Function
Prog.
no.
Level
1)
Standard value
Sensor input BX1
None | DHW sensor B31 | Collector sensor B6 | DHW circulation sensor
B39 | Buffer sensor B4 | Buffer sensor B41 | Common flow sensor B10 |
Solid fuel boiler sensor B22 | DHW charging sensor B36 | Buffer sensor
B42 | Common return sensor B73 | Cascade return sensor B70 | Swim-
ming pool sensor B13 | Solar flow sensor B63 | Solar return sensor B64
5930
C
Collector sensor B6
Sensor input BX2
Parameters see Sensor input BX1 (prog.-no. 5930)!
5931
C
DHW sensor B31
Sensor input BX3
Parameters see Sensor input BX1 (prog.-no. 5930)!
5932
C
Buffer st tank sensor B4
Function input H1
None | Optg mode change HCs+DHW | Optg mode change DHW |
Optg mode changeover HCs | Optg mode changeover HC1 | Optg
mode changeover HC2 | Optg mode changeover HC3 | Heat genera-
tion lock | Error/alarm message | Consumer request VK1 | Consumer
request VK2 | Release swi pool source | Excess heat discharge | Re-
lease swi pool solar | Operating level DHW | Operating level HC1 | Op-
erating level HC2 | Operating level HC3 | Room thermostat HC1 |
Room thermostat HC2 | Room thermostat HC3 | DHW thermostat |
Pulse count | Checkb sign flue gas damper | Start prevention | Con-
sumer request VK1 10V | Consumer request VK2 10V | Preselected
output 10V
5950
C
None
Contact type H1
NC | NO
5951
C
N/O contact
Voltage value 1 H1
5953
E
0,5
Function value 1 H1
5954
E
0
Voltage value 2 H1
5955
E
10
Function value 2 H1
5956
E
1000
Function input H4
None | Optg mode change HCs+DHW | Optg mode changeover DHW |
Optg mode changeover HCs | Optg mode changeover HC1 | Optg
mode changeover HC2 | Optg mode changeover HC3 | Heat genera-
tion lock | Error/alarm message | Consumer request VK1 | Consumer
request VK21 | Release swi pool source | Excess heat discharge | Re-
lease swi pool solar | Operating level DHW | Operating level HC1 | Op-
erating level HC2 | Operating level HC3 | Room thermostat HC1 |
Room thermostat HC2 | Room thermostat HC3 | DHW thermostat |
Pulse count | Checkb sign flue gas damper | Start prevention | Flow
measurement Hz
5970
C
None
Contact type H4
NC | NO
5971
C
N/O contact
Frequency value 1 H4
5973
E
0
Function value 1 H4
5974
E
0
Frequency value 2 H4
5975
E
0
Function value 2 H4
5976
E
0
Programming
396532 05.11
Paramount three 30-115 kW
59
Содержание Gas condensing boiler
Страница 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Страница 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Страница 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Страница 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Страница 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Страница 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...