Duration of the quick setback for setback by
2
°C in h:
Outside temperature mixed:
Time constant building (Configuration, prog.no. 6110)
0 hrs
2 hrs
5 hrs
10 hrs
15 hrs
20 hrs
50 hrs
15°C
0
3.1
7.7
15.3
23
10°C
0
1.3
3,3
6.7
10
13,4
5°C
0
0.9
2,1
4,3
6,4
8.6
21.5
0°C
0
0,6
1,6
3,2
4,7
6.3
15.8
-5°C
0
0,5
1.3
2,5
3.8
5
12.5
-10°C
0
0,4
1
2,1
3.1
4.1
10.3
-15°C
0
0,4
0.9
1.8
2,6
3,5
8.8
- 20 °C
0
0,3
0,8
1,5
2,3
3.1
7.7
Duration of the quick setback for setback by
4
°C in h:
Outside temperature mixed:
Time constant building (Configuration, prog.no. 6110)
0 hrs
2 hrs
5 hrs
10 hrs
15 hrs
20 hrs
50 hrs
15°C
0
9,7
24.1
10°C
0
3.1
7.7
15.3
23
5°C
0
1,9
4,7
9.3
14
18.6
0°C
0
1.3
3,3
6.7
10
13,4
-5°C
0
1
2,6
5,2
7,8
10.5
26.2
-10°C
0
0.9
2,1
4,3
6,4
8.6
21.5
-15°C
0
0,7
1.8
3.6
5.5
7.3
18.2
- 20 °C
0
0,6
1,6
3,2
4,7
6.3
15.8
Optimum start control max
(790, 1090, 1390)
Optimum stop control max
(791, 1091, 1391)
The optimization of the on/off switching time is a function of time and possible
with or without the room unit. With a room unit the conversion of the operating
level compared to the programmed time point is moved forward so that the
building dynamics (heat up and cool down time) is considered. In this way the de-
sired temperature level is reached exactly at the programmed time point. If this is
not the case (too early or too late) a new switching time point is calculated which
is used the next time.
Without a room sensor an advance time point is calculated based on the outside
temperature and the building time constant (prog. no. 6110). The optimization
time (advance) is limited here to a maximum value. By setting the optimization
time = 0, the function is switched off.
Programming
396532 05.11
Paramount three 30-115 kW
77
Содержание Gas condensing boiler
Страница 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Страница 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Страница 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Страница 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Страница 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Страница 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...