5.15 Controller Stop Mode
(Manual Adjustment of
Burner Load)
For setting and controlling the CO
2
values the Paramount in operated in the
con-
trol stop function
.
1.
> 3 s
Boiler temperature
Press operation mode button Heating Operation for
approximately 3 seconds
=> the message
Controller Stop Function ON
is displayed.
2. Wait, until the display has reached the basic display again.
3.
Press information button
=> The message
Controller stop setpoint adjust
appears in the display. The ac-
tual modulation degree will be displayed on the display.
4. Press OK button
= > The nominal value can now be changed.
5. Press OK button
=> The displayed nominal value is taken over by the control.
Note:
The regulator stop function is stopped by pressing the
operating mode but-
ton Heating Operation
for approximately 3 seconds, reaching the maximum boiler
temperature or a time limit.
If a heat demand from a cylinder with internal indirect coil is present, this demand
will continue to be met while the controller stop function is running.
5.16 Guide Values for Injector
Pressure
Guide values for gas flow, jet presure and CO
2
-content
The values given in
Tab. 5 (Page 31)
are guide values. It is important that the gas
quantity is set via the injector pressure in such a way that the CO
2
-value is within
the specified values (see
Tab. 2 (Page 12)
).
Installation
30
Paramount three 30-115 kW
396532 05.11
Содержание Gas condensing boiler
Страница 1: ...Installation operation and maintenance manual Gas condensing boiler Paramount three 30 115 kW ...
Страница 21: ...Fig 5 Connection plan Prior to installation 396532 05 11 Paramount three 30 115 kW 21 ...
Страница 24: ...4 8 Legend Prior to installation 24 Paramount three 30 115 kW 396532 05 11 ...
Страница 133: ...Space for notes 396532 05 11 Paramount three 30 115 kW 133 ...
Страница 134: ...Space for notes 134 Paramount three 30 115 kW 396532 05 11 ...
Страница 135: ...Space for notes 396532 05 11 Paramount three 30 115 kW 135 ...