![POLIURS CV4.04 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/poliurs/cv4-04/cv4-04_montage-instructions_1574149026.webp)
HEATING MAIN MONTAGE INSTRUCTIONS CV4.04
8.2.1. ELECTRO-WELDING CONNECTION MONTAGE
Necessary materials:
- heat-shrinkable PE sleeve;
- welding bands – 2 pieces;
- A and B components – 2 pieces;
- PE cork - 2 pieces;
- materials for alarm system installation (when planned).
Montage equipment and instruments:
- electro-welding machine with steel clapms and electric cable;
- gas torch;
- soldering burner (for alarm wires);
- measuring bowl - 2 pieces;
- bowl for mixing and filling of components;
- mixer;
- sand paper (rough on fabric base);
- degreasing liquid (for example: toluol);
- brush or a rag;
- protective goggles and gloves;
- hand drilling machine;
- drills: Ø27,5 mm, Ø25 mm and Ø3 mm;
- PE electronic cork welder;
- megahommeter for alarm system testing.
Montage sequence:
1. Centralize the shrinkable casing over
the joint area and mark the ends of
the casing all the way around the
jacket pipe. Grind the ends with an
emery cloth – grain 40. Clean the
jacket pipe with ethyl alcohol after
grinding.
2. Mount the copper welding band
around the jacket pipe, app. 30 mm
from the casing mark. Ensure a
distance of 6-8 mm between the band
ends.
3. Place casing over the welding bands.
Bend the terminals 45° away from
each other.
8.2.5.