What the Eagle™ Records
••••
55
while still giving single-cycle response. If event change detailed
disturbance information on a cycle basis is required, use the event
change report. Event change gives much more detail, but is more
complicated to examine. The timestamp of a significant change
event can be used to find the same disturbance in the event
change report for further analysis.
For even more detail, waveform capture can be used (if enabled).
If the disturbance triggered waveform capture, the raw waveforms
of each voltage and current channel can be displayed. Again, the
significant change timestamp is used to find the waveform in the
list of captured waveforms.
Event Change
The event change report provides detailed cycle-level information
about each voltage disturbance. This is the most detailed report
available short of actually looking at raw waveforms with
waveform capture. An event is triggered when the voltage moves
past any of a series of trip points. Maximum and minimum
voltages and currents during the event, the event duration (in
cycles), and the current before and after the event are all
recorded.