Poor transfer of the flame from the main
burner
Check the position of the blocks of wood / debris
If necessary, remove dust and dirt from the holes
of the burner
Extinguishing of the flame at the
ionization electrode (braising or picking
of the flame)
Check the tightness of the fireplace combustion
chamber, proper adhesion of glass to each other
on the edges, as well as correct position of the
seals and downforce strip
Check restrictor setting
No good flame under ionization pin
(suffocating flame)
Check position blocks/chips
Ionisation electrode not inserted
correctly
Place the electrode in the right place
Blocked ionization electrode (measure
ionization current flow, when> 0 and
<1.8 uA)
Remove any residue vermiculite or debris from the
burner
Faulty ionisation electrode (measure
ionisation current if 0 electrode is
damaged)
Replace the ionisation electrode
Triggered shock sensor (shake)
Check the sensor connection. Check whether the
construction of the fire housing has not been
damaged (cracked)
F12
There has been no release of
ESYS
ESYS under permanent blockade
Wait half an hour until ESYS resets itself
F13/F14 (ionisation <0.8 µA) Flame
loss when only the main
burner (F13) is on or both
burners (F14) are on
Too low gas pressure or no gas in the
system
Check the gas supply
Damage to the coil of the gas valve
Replace the coil of the gas valve
Throttling flame
Check the patency of the combustion air system
24 hour control
Reset using the remote control
Ionisation pin short-circuited
Remove chips, vermiculite or glow material lying
against the ionisation pin
Ionisation current too critical
(0.8 ≤ Iionisation < 1.8 µA)
Increase ionisation current to ≥ 1.8 µA by
rearranging vermiculite, and removing chips and
dust from the burner openings
F15
No automatic control ESYS
Loosening of the automation control
Fix the automatic control
Not properly installed automatic control Install properly automatic control
High Limit error
Electrodes by the gas adjustment block
connector are bent
Straighten them
Damage to the bridge of the upper limit Check the bridge of the upper limit ESYS
F16
Hardware failure ESYS
Damage ESYS (burner module)
Exchange ESYS (burner module)