Philadelphia Scientific
®
iBOS
®
Pro 6 Series Installation Manual
Page 29 of 84
5.3.4 Connect Sentinel
™ to charger
Make sure charger is turned off.
Remove the tubing from the ends of the
Quick Tap.
Pull the charger cables apart from each other
and insert the cable connector in between.
Place the Quick Tap between the cables on
the charger and squeeze.
Keep the pins centered on the cable and
push the cables fully to the bottom of the
recess allowing the pin to completely
penetrate into the cable.
Be careful to not bend the pins.
Ensure the pins of the Quick Tap fully
penetrate the charger cables and secure with
four wire-ties.
Verify the amber LED illuminates with a
battery connected. If not, check the pins on
Quick Tap have not bent during install.
Note: if the connector is re-installed or replaced, do not
use the same holes for the electrical connection. Better
electrical connection is achieved by making a new set of
holes.
Quick Tap Installation Diagram