Assembly and Operation Manual
If intrusion detector is not connected, you must install the jumper between pins
DETECTOR
and
GND
to the “
XT1.L
” connector block. On delivery, this jumper is installed.
5.9.3 If the turnstile is locked (the “
Always locked
” mode /“
Both directions closed
” mode
when both directions are locked, Tables 2 and 3) and a signal comes from the intrusion
detector, the “
Alarm
” signal is generated. The “Alarm” signal is disabled after 5 sec. or by
executing of any received command.
The signal from the intrusion detector is ignored for
the period of authorized unlocking of the turnstile in either or both directions.
If within 3 sec. after the “
Always locked”/“Both directions closed
” mode is set, the signal
from the intrusion detector comes, it is also ignored.
The intrusion detector status signal is constantly transmitted to the “
Det Out
” and
“
Common
” contacts of the CLB “
XT1.H
” connector block (Fig. 4).
5.9.4 The emergency unblocking device is connected to the “
XT1.L
” connector block of the
CLB in accordance with the connection layout (Fig. 4 and Fig. 11). If the “
Fire Alarm
” input
is not used, it is necessary to set a jumper between the contacts “
Fire Alarm
” and “
GND
”.
This jumper is preset at the factory.
Operation of the turnstile under commands of the emergency unblocking device is
stipulated in clause 5.10.
5.9.5 The remote indicators
**)
are connected to the connector blocks “
XT4
” (“
Light A
”) and
“
XT5
” (“
Light B
”). At that the “
Light A
” (“
Light B
”) relay is active (the voltage is supplied to
the relay coil), when the “Green arrow” pictogram on the LED indication display,
corresponding to the set passage direction, lights, and it is passive, when the “Green
arrow” pictogram on the Led display does not light. The response/release of the relays
“Light A” and “Light B” can be defined according to lighting up/going down of the red
indicators, which are installed near the above mentioned relays (Fig. 4). Output cascades
for the “Light A” and the “Light B” relays are non bridging relay contacts (Fig. 8) with the
following signal characteristics:
maximum switched voltage ............................................................................ 30 VDC
maximum switched voltage .............................................................................42 VAC
maximum switched AC/DC.................................................................................... 3 A
closed contact resistance
...................................................................
max. 0.15 Ohm
Figure 8. Output cascades for Light A and Light B
14