background image

TTR-07.1 Electromechanical Tripod Turnstile

 

 

Note: 

For generating of a high-level signal at all the input contacts (

Unlock A

Stop

Unlock B

Fire Alarm

 and 

Detector

) 2kOhm resistors connected to the power supply 

bus “+ 5V” are used. 

The control element* must provide the following signal characteristics: 

* the relay contact as the control element: 

minimum switched current ........................................................................max. 2 mA 
closed contact resistance  
(with the resistance of the connected cable)  ...................................... max. 300 Ohm 

*the circuit with open-collector output as the control element: 

voltage at the closed contact  
(low - level signal at the CLB input)  ...........................................................max. 0.8 V 

5.4.3 The relays PASS A (contacts 

PASS A

 and 

Common

), 

PASS B

 (contacts 

PASS 

В

 

and 

Common

), 

Ready

 (contacts 

Ready

 and 

Common

), 

Detector

 (contacts 

Det Out

 and 

Common

) and 

Alarm

 (contacts 

Alarm 1

 and 

Alarm 2

) have normally open contacts. The 

Common

” contact, at that, is not connected to the CLB power supply negative terminal. In 

the initial (inactive) state, when the power is on, the relay contacts “

PASS A

”, “

PASS B

”, 

Ready

” and “

Detector

” are closed (voltage is supplied to the relay coil) and the “

Alarm

” 

relay contacts are broken (voltage is not supplied to the relay coil). The CLB relay 
operation/release is indicated by lighting up/going down of the red test indicators located 
near the corresponding relays (Fig. 4). The output cascades for 

PASS A

PASS B

Ready

Det Out

 and 

Alarm

 are the contacts with the following signal characteristics (Fig 7): 

maximum commutation voltage ................................................................................ 42 VDC 
maximum switched current ......................................................................................... 0.25 A 
closed contact resistance.............................................................................. max. 0.15 Ohm 

 

Figure 7.   Output cascades for PASS A, PASS B, Ready, Det Out and Alarm  

5.5  Control modes of the turnstile  

5.5.1 There are two modes of the turnstile control - a pulse control mode and a potential 
control mode. They determine available operating modes

 

of the turnstile

 

(Table 2 and 

Table 3). 
5.5.2 The control mode is set by the jumper on the J1 connector (the J1 connector location 
is shown on Fig. 4 and on a label located on the inner surface of turnstile cover (2)): the 
jumper is fixed — the pulse control mode, the jumper is not fixed — the potential control 
mode. The jumper is fixed at the factory before the delivery. 

11 

Содержание TTR-07.1

Страница 1: ...ASSEMBLY AND OPERATION MANUAL TTR 07 1 Electromechanical Tripod Turnstile with Automatic Anti Panic Arms...

Страница 2: ...Electromechanical Tripod Turnstile with Automatic Anti Panic Arms TTR 07 1 Assembly and Operation Manual...

Страница 3: ...ency unblocking of the turnstile 15 5 11 Operation contingencies and response 15 6 MARKING AND PACKAGING 16 7 SAFETY REQUIREMENTS 16 7 1 Installation safety requirements 16 7 2 Operation safety requir...

Страница 4: ...el WRC wireless remote control CLB control logic board 1 APPLICATION The TTR 07 1 electromechanical tripod turnstile with automatic anti panic folding arms hereinafter the turnstile is designed for ma...

Страница 5: ...rotation force max 3 kgf RC panel cable length1 min 6 6 m Ingress Protection Rating IP41 under EN 60529 Electric shock protection class III IEC 61140 Mean time to failure min 4 000 000 passages Mean...

Страница 6: ...adhesive cable tie mount 3 Technical documentation Certificate 1 Assembly and operation manual 1 Package Box 1 4 2 Optional equipment supplied on request WRC kit includes a receiver and transmitter t...

Страница 7: ...on display 3 hub 4 hub fastening bolts 5 barrier arm 6 AC power cable 7 turnstile power supply 8 turnstile power cable 9 emergency unblocking device Fire Alarm 10 emergency unblocking device cable 11...

Страница 8: ...current minimum 6 A in 5 sec 5 2 Design The design of the turnstile is shown in Fig 2 Numbers in brackets correspond to Fig 2 of this Manual 5 2 1 The turnstile comprises a turnstile housing 1 with s...

Страница 9: ...dard e g the terminal is placed at the backside of the turnstile housing the RC panel orientation towards the turnstile can be changed by exchanging places of the RC wires to the contacts Unlock A and...

Страница 10: ...be connected to the turnstile as follows any device separately in any combination with each other all devices simultaneously in parallel Note At the parallel connection of the above devices to the tur...

Страница 11: ...es indication on the RC panel Led A Led Stop and Led B the signal of hub turning in the corresponding direction PASS and PASS the signal of the turnstile ready for a current command Ready the alarm ou...

Страница 12: ...ntacts PASS A PASS B Ready and Detector are closed voltage is supplied to the relay coil and the Alarm relay contacts are broken voltage is not supplied to the relay coil The CLB relay operation relea...

Страница 13: ...Appendix B The minimum input signal duration when the operating mode can be changed should be 100msec The passage waiting time is equal to the low level signal duration the turnstile remains open in...

Страница 14: ...nel 5 7 3 The WRC operation manual is supplied with that device 5 8 Operation with an ACS controller 5 8 1 In the pulse control mode control over the turnstile with an ACS controller is similar to tha...

Страница 15: ...n accordance with the connection layout Fig 4 and Fig 11 If the Fire Alarm input is not used it is necessary to set a jumper between the contacts Fire Alarm and GND This jumper is preset at the factor...

Страница 16: ...further standard operation 5 11 Operation contingencies and response 5 11 1 The turnstile is capable of providing information on the following operation contingencies unauthorized access passage dela...

Страница 17: ...uirements The installation should be carried out only by the qualified personnel after careful study of this Manual Warning All the cables should be connected up when the power supply is switched off...

Страница 18: ...tion on less steady foundation frame foundation for example to mark the mounting holes according to Fig 10 to control the vertical position of the turnstile during installation to arrange additional e...

Страница 19: ...rrent 6 A for compliance with Chapter 3 turnstile operating voltage 8 4 Installation procedure The following installation procedure complies with given installation recommendations see clause 8 1 1 Un...

Страница 20: ...6 Install the hub 3 and the barrier arms 5 in the following order Insert the hub into a corresponding mounting face on the turnstile mechanism shaft Caution For proper hub installation before the fin...

Страница 21: ...ntinuous signal will sound when the intrusion detector activates To eliminate that sound signal press any button on the RC panel The sound will stop without pressing the button in 5 0 5 sec 14 Set the...

Страница 22: ...TTR 07 1 Electromechanical Tripod Turnstile Figure 11 Connection layout description is given in Table 1 21...

Страница 23: ...arm should be fixed automatically 9 2 Operating modes of the turnstile in pulse control mode See Table 2 for the operating modes set from the RC PANEL and for the corresponding indication Please note...

Страница 24: ...ked in the direction of completed passage 4 Free passage in the set direction open for free passage in the chosen direction Press the STOP button and the button corresponding to the chosen passage dir...

Страница 25: ...ntact corresponding to the set passage direction the turnstile remains open in the set direction 3 Both passage directions are open the turnstile is open for passage in both directions The low levels...

Страница 26: ...e the outer panel Check the power cable serviceability and reliability of its connection to the CLB XT3 connector block The turnstile is not controlled in one of the directions and there is light indi...

Страница 27: ...ation axis Note Avoid the ingress of lubricant on the arm rotation sensor disc and the roller surfaces 5 Check the reliability of the cable connections to the CLB connector blocks ling When the cover...

Страница 28: ...amper holder 21 optical arm rotation sensor 11 TRANSPORTATION AND STORAGE The turnstile in the original package should be transported in closed freight containers or in other closed type cargo transpo...

Страница 29: ...the passage direction B opens either for 5 sec or until the passage has been effected in this direction or until the command Always locked and the status of the passage direction A does not change The...

Страница 30: ...at the contact Unlock A while there is a low level at the contacts Unlock B and Stop or active front is at the contact Unlock B while there is a low level at the contacts Unlock A and Stop or active f...

Страница 31: ...open for passage in the direction There is a low level at the contact Unlock while there is a high level at the contacts Stop and Unlock At this command the direction B opens till the low level signal...

Страница 32: ......

Страница 33: ...PERCo Polytechnicheskaya str 4 block 2 194021 Saint Petersburg Russia Tel 7 812 247 04 64 E mail export perco com support perco com www perco com...

Страница 34: ...www perco com...

Отзывы: