AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
27
.9.20
13
85
EC-flags (16-bit)
Information!
Available only with AS-i PROFIsafe Gateways.
EC-flags (16-bit)
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
byte 0
DA
NSE
OV
EF
–
–
–
Pok
byte 1
OR
APF
NA
CA
AAv
AAs
S0
Cok
Tab. 13-16.
DA: Double address
NSE Noise
OV: Overvoltage
EF: Earth falut
Pok: Periphery_Ok
OR: Offline_Ready
APF: APF
NA: Normal_Operation_Active
CA: Configuration_Active
AAv: Auto_Address_Available
AAs: Auto_Address_Assign
S0: LDS.0
Cok: Config_Ok
byte 0
DA 0 = OK
1 = Double address
NSE 0 = OK
1 = Noise
OV 0 = OK
1 = Overvoltage
EF 0 = OK
1 = Earth falut
Pok 0 = OK
1 = Periphery fault
byte 1
Cok 0 = OK
1 = ’Config Error’
S0 1 = Address ’0’ present
0 = Adresse ’0’
not
present
AAs 1 = ’Auto_Address_Assign’
not
active
0 = ’Auto_Address_Assign’ active