AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Function and startup of the Safety Monitor
27
.9.20
13
71
The menu can be exited by pressing the ESC/Service key without changing the
data.
10.8.2
Safe data
This section describes the system behavior of the safe unit when using the chip
card.
In general the safe part of the chip card has 4 memory banks (A…D). A bank is
referred to as an active bank. Unless otherwise stated, the operations described
in the following are always performed on the active bank.
10.8.2.1 Data incompatible
If a card with incompatible data is found, the following error message is output:
10.8.2.2 Data compatible
If a card with an empty active memory bank is found, the safety configuration in-
cluding code sequences is written to the card and in future all changes are made
in the card and in the device at the same time. The following message is dis-
played on the device:
CHIPCARD AND
AS-I DATA
DIFFERENT
CARD->MASTER
MASTER->CARD
CONTINUE
Description
CHIP CARD>MASTER: Chip card data are copied to the master
MASTER->CHIPCARD: Master data are copied to the chip card
NEXT: No change to the data
CHIPCARD NOT
COMPATIBLE
CHIPCARD FOUND.
SAFETY DATA WILL
BE SYNCHRONIZED
Содержание VBG-PN-K30-D-S16
Страница 1: ...AS I 3 0 PROFINET GATEWAY WITH INTEGR SAFETY MONITOR FACTORY AUTOMATION MANUAL...
Страница 41: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Installation 27 9 2013 41 1 new old 2 3...
Страница 125: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples 27 9 2013 125...
Страница 126: ...27 9 2013 126 AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples...
Страница 130: ......