AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
27
.9.20
13
95
13.4
PROFINET diagnostics
Description of the diagnostic data which are sent via the PROFINET diagnostics
channel.
13.4.1
Channel error codes
Slot chan-
nel
error
type
error text
help text
0
AS-i
Master
16
configuration error
the actual configuration found on AS-i
does not match the projected configu-
ration, or the AS-i master performs
startup operations.
17
slave 0 detected
there is an AS-i slave with zero
address
18
no auto address
assignment
automatic address assignment would
not be possible
19
auto address
assignment availa-
ble
as soon as an appropriate slave is
connected, its address will be auto-
matically assigned
20
configuration mode
the AS-i master is in configuration
mode
21
no normal operation the AS-i master is performing startup
operations
22
AS-i power fail
the AS-i power supply is insufficient
23
off-line
the AS-i master doesn't send tele-
grams on AS-i
24
peripheral fault
at least one AS-i slave reports a
peripheral fault, or the AS-i master
performs startup operations
25
earth fault
the AS-i is short-circuited to ground
26
overvoltage
the AS-i is short-circuited to an higher
potential
27
noise
the AS-i signals are noisy
28
duplicate address
at least two AS-i slaves answers on
the same address
Tab. 13-27.
AS-i Master
0: circuit 1
1: circuit 2
Содержание VBG-PN-K30-D-S16
Страница 1: ...AS I 3 0 PROFINET GATEWAY WITH INTEGR SAFETY MONITOR FACTORY AUTOMATION MANUAL...
Страница 41: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Installation 27 9 2013 41 1 new old 2 3...
Страница 125: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples 27 9 2013 125...
Страница 126: ...27 9 2013 126 AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples...
Страница 130: ......