![Pepperl+Fuchs ICE1-8IOL-S2-G60L-V1D Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/pepperl-fuchs/ice1-8iol-s2-g60l-v1d/ice1-8iol-s2-g60l-v1d_manual_1527666053.webp)
The Integrated Web Server
2
0
2
0
-0
6
53
Device Overview
The left side shows a graphical representation of the module with all LEDs and the positions of
the rotary coding switches
Device Information
The "Device Information" table contains some basic data on the module, e.g., the variant, the
state of the cyclic communication and a diagnostic indicator. This indicates whether a diagno-
sis is present in the module.
Port Information
The "Port Information" table shows the configuration and status of all IO ports of the module.
Force Mode
Force Mode can be helpful when commissioning the machine or during fault repair within the
machine. The data for the input and output channels can be overwritten and set independently
via the web server. It is therefore possible to set each output manually and simulate each input,
regardless of the process data output from the controller or the actual status of the physical
input.
You can activate "Force Mode" with the "Switch on" button. It can be used across the board in
offline mode without a connection to the controller, or in online mode with a connection to the
controller. If you leave the status page or the web server, "Force Mode" automatically switches
off. To enable force mode, enter user "admin" with the password "private."
In offline mode, you can configure the port mode via the wrench icon. The following modes are
available when doing so:
•
Inactive
•
Digital Input
Column
Information
Port
Description of the port
Type
Type of IO-Link port. This may be class A or class B depending on the
variant. The suffix "+DI" or "+DO" indicates that an additional digital
input or digital output is available.
Pin / Channel
The corresponding pin on the M12 slot
Function
The current port configuration.
These can be changed via the web browser, the control panel or an
IO-Link device tool.
State
Current state of the respective pins. In the case of digital inputs or out-
puts, ON or OFF is displayed here. For IO-Link connections, the COM
status is displayed.
Dia
The diagnostic indicator shows whether a diagnosis is available for
this channel.
Details
This icon takes you directly to the corresponding detail view for this
port. More information is available there.
Caution!
Serious injuries or property damage
Improper use of the "Force Mode" function can result in serious injury or property damage. Be
careful when you use the "Force Mode" function. Please consider the consequences of using
it.
Note
User authentication is required to use "Force Mode." Users can be created and changed on the
system side. The default password for the "admin" user is "private."