Commissioning for PROFINET
2
0
2
0
-0
6
51
•
DO 5B = digital output connection 1, channel B (pin 2)
•
DO 1A optional = optional when configured as the DO and the
general device
parameter
"Digital Out Channel A Controlled by"
is set to
Status/Control Module
.
Mapping the IO Channel to the PROFINET Channel Diagnostics
IO-Link Connections Process Data, Slot 1/Subslot 2 ... Subslot 9
The process data lengths of the IO-Link connections in COM mode depend on the configura-
tions of IO-Link connections X1 ... X8. Data lengths between 1 ... 33 bytes of input data and/or
1 ... 32 bytes of output data can be configured.
The data content can be taken from the descriptions of the IO-Link devices.
If no precise data length exists for the IO-Link device configuration, always select the next larg-
est data length.
The mapping mode selected for the status/control module has no influence on the process
data of the IO-Link connections.