Commissioning, Protocol Setting
EtherNet/IP
If you use EtherNet/IP as the protocol, use rotary switch X100 to set the value 100 as the last
octet of the IP address for the module. You can use rotary switch X100 to set a value of 0 to 2
for the IP address. You can use rotary switches X10 and X1 to select values between 0 and 9.
You can use rotary switch X10 to configure position 10 of the last octet of the IP address. You
can use rotary switch X1 to configure position 1 of the last octet of the IP address.
The default setting for the first three octets of the IP address is 192.168.1.
Example
: Rotary switch settings 2 (X100), 1 (X10), and 0 (X1) result in an IP address of
192.168.1.210 for EtherNet/IP.
PROFINET
If you use PROFINET as the protocol, only set rotary switch X100 to the value "P."
Factory Settings
A factory reset erases any changes you have made to settings, etc. and restores the factory
settings. The saved protocol selection is also reset.
To perform a factory reset, set rotary switch X100 to 9, rotary switch X10 to 7, and rotary switch
X1 to 9. Then switch the module off and on again. The factory settings are restored after 10
seconds.
To select a new protocol, follow the instructions in this chapter.
Figure 4.2
Restoring factory settings: X100 = 9, X10 = 7, X1 = 9
2
0
X
1
0
X
X03
X4
X8
7
X
3
X
X6
5
X
1
X
X2
A
DIA
B
XE
X04
BF
DIA
Lnk/Act
P2
P1
U
S
A
DIA
B
A
DIA
B
A
DIA
B
x100
x10
x1
MS NS
0 E/IP
P
0
0
X100
0
E/IP
P
X10
X1
9
1
2
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
Caution!
Destruction of the Operating System
When restoring the factory settings, ensure that the module is connected to the voltage supply
and switched on for
at least
10 seconds. If it has been on for less than 10 seconds, the operat-
ing system may be destroyed. The module would then need to be sent to Fuchs for
repair.