Commissioning for PROFINET
Figure 5.26
The port interconnection was successful if the link is shown in the "Topology View" and on
the "Partner Port."
5.2.9
Identification and Maintenance Functions (I&M)
The PROFINET module is capable of uniquely identifying devices installed in the system by
means of an electronic nameplate. This device-specific data can be read acyclically at any time
by the user. In addition, the installation date, location code, and other descriptions can be
defined in the module on creation of the system.
Supported I&M Functions
•
Module-specific I&M functions
The module-specific I&M features 0 to 4 can be read or written via slot 0. The specified
index is used for the mapping of data records.
I&M 0
Data object
Length
[byte]
Access Default value/description
MANUFACTURER_ID
2
Read
0x005D
ORDER_ID
20
Read
Order number of the module in
ASCII
SERIAL_NUMBER
16
Read
Defined in the production process, in
ASCII
HARDWARE_REVISION
2
Read
Hardware revision of the device
SOFTWARE_REVISION
4
Read
Software revision of the device
REVISION_COUNTER
2
Read
Counts each statically stored param-
eter change on the IO-Link master
(e.g., device name or IP address)
PROFILE_ID
2
Read
0xF600 (generic device)
PROFILE_SPECIFIC_TYPE
2
Read
0x0003 (IO module)