Commissioning for PROFINET
Figure 5.19
5.2.6.5
Digital Input Logic
This parameter can be used to configure the logic of channels that are used as digital inputs.
•
Default setting
:
NO (normally open) for all channels
•
NO (normally open)
:
In this case, an undamped sensor has an open switching output (low signal).
The device input detects a low level and returns a 0 to the control unit.
•
NC (normally closed)
:
In this case, an undamped sensor has a closed switching output (high signal).
The device input detects a high level, inverts the signal, and returns a 0 to the control unit.
Figure 5.20
5.2.6.6
Digital-IO-mode for Ch. B/Pin 2
In this area, you can parameterize the IO-Link connections of ports 5 ... 8, class B, as follows:
Figure 5.21