Commissioning for PROFINET
2
0
2
0
-0
6
31
•
Pull alarms
COM fault
: no IOL device
If the option is set to "Disabled," a channel diagnosis is generated when an IO-Link device is
lost.
Default: Enabled
Port Mode
•
Disabled
Configure an IO-Link port for later use using the "Disabled" option. If the IO-Link device is
not connected, no diagnosis is generated.
•
IO-Link Autostart
No explicit port configuration is required with the "Plug&Play" option. Basic assignments
are not required. Examples:
•
Validation and backup (test level)
•
Port cycle time
•
Manufacturer identifier
•
Device ID
•
IO-Link Manual
An explicit port configuration is possible for specific assignments.
•
Validation and backup (test level)
•
Port cycle time
•
Manufacturer identifier
•
Device ID
These parameters are GSD-based and can be configured via the PROFINET engineering
system.
Default: IO-Link Autostart
Overview of Dependencies for the "Port Mode" Configuration Type
Validation and Backup
The "IO-Link Manual" port mode is required for the "Validation and Backup" option.
•
No IOL device check
The connected "Manufacturer identifier" and "Device ID" are not checked.
No "Backup and Restore" of the IOL master parameter server is supported.
Feature
IO-Link Autostart
IO-Link Manual (GSD)
Access on process data (PD) Yes
Yes
Diagnostics of port & device
Yes
Yes
I&M data (IM0) access
Yes
Yes
Device check (consoli-
dated/real)
No
Yes
Backup & Restore
No
Yes
Device parameterization
(PDCT)
No
No
TMG TE GmbH Device Tool
V5
Yes
Yes
Commissioning (online)
No
No
Table 5.1
Port mode configuration types