72
G. OPERATION – MODBUS INTERFACE
1.
Modbus Configuration:
The table below summarizes the Modbus
configuration details:
2.
Modbus Holding Registers:
Modbus communicates using “words” (the contents of
16 bit holding registers). The 852-1 Interface Adapter
organizes the data in read-only holding registers. Table
2 shows the information that is available for reading
and the address of the holding registers. Depending on
the type of Modbus software used, the holding register
addressing range starts at either 0x0000 or 0x0001.
The values of STATE and ERROR_NUMBER can
be used to determine whether the boiler control is
operating correctly, not communicating or in an
error state.
APPENDIX D. 852-1 INTERFACE ADAPTER
Table 2
Table 1
Modbus Configuration Specifications
Protocol
Modbus RTU
Default Address
0x01 (settable with SiteVision)
Supported Commands
• Read Holding Registers (0x03)*
• Write single holding register (0x06)
Baud Rate
9600 bps
Data Length
8 bits
Parity
None
Stop Bits
1
Physical Layer
RS485 (2 wire)
Modbus 1 A Connection
J7-1
Modbus 1 B Connection
J7-3
Buffer Size
8 registers per frame
Modbus Holding Registers (Read Only)
Item Index
Parameter Name
Address & Holding Registers
Notes
Word
byte
Range Start
0x0000
Range Start
0x0001
0 High byte
0
STATE
0x0000
0x0001
See Table 3
0 Low byte
1
STATUS
0x0000
0x0001
See Table 4
2 High byte
2
ERROR_NUMBER
0x0002
0x0003
See Table 6
2 Low byte
3
WARNING_NUMBER
0x0002
0x0003
See Table 7
4 High byte
4
FLOW_TEMP*
0x0004
0x0005
°C = byte value
2
–10
°F = °Cx9
5
+32
4 Low byte
5
RETURN_TEMP
0x0004
0x0005
6 High byte
6
DHW_TEMP
0x0006
0x0007
6 Low byte
7
FLUE_TEMP
0x0006
0x0007
8 High byte
8
NOT USED
0x0008
0x0009
8 Low byte
9
NOT USED
0x0008
0x0009
10 High byte
10
APPLIANCE_TYPE
0x000A
0x000B
—
10 Low byte
11
CONTROL_CONFIG_BYTE
0x000A
0x000B
—
12 High byte
12
NOT USED
0x000C
0x000D
—
12 Low byte
13
DHW_MODE
0x000C
0x000D
—
14 High byte
14
NOT USED
0x000E
0x000F
—
14 Low byte
15
DHW_SETPOINT
0x000E
0x000F
—
* FLOW_TEMP is the boiler supply (outlet) water temperature.
To read these values, issue a Modbus command to read a holding register. For example, if a command is issued to read
0x0000 the resulting, unsigned word may read, “0x090F”. The high byte for this word is “0x09”. Table 3 shows that this value
indicates that the burner is on. The low byte for this word is “0x0F”. This indicates that the boiler is on as a result of the freeze
protection algorithm as shown in Table 4.
Содержание PUREFIRE PFW-199
Страница 20: ...18 WATER PIPING AND CONTROLS Figure 4 3 Schematic Piping One Boiler with a Single Storage Tank...
Страница 21: ...19 WATER PIPING AND CONTROLS Figure 4 4 Schematic Piping One Boiler with Multiple Storage Tanks...
Страница 22: ...20 Figure 4 5 Schematic Piping Two Boilers with a Single Storage Tank WATER PIPING AND CONTROLS...
Страница 23: ...21 WATER PIPING AND CONTROLS Figure 4 6 Schematic Piping Two Boilers with Multiple Storage Tanks...
Страница 24: ...22 WATER PIPING AND CONTROLS Figure 4 7 Schematic Piping Alternate Piping with Patented Anti Scale System...
Страница 33: ...31 Figure 7 3 Internal Wiring Schematic for PFW 199 PFW 210 PFW 399 Boilers ELECTRICAL CONNECTIONS...
Страница 47: ...E LIGHTING OPERATING PROCEDURES 45 Figure 9 4 Lighting Operating Instructions START UP PROCEDURE...
Страница 60: ...58 Figure 13 2 Heat Exchanger Burner Assembly Repair Parts REPAIR PARTS...
Страница 63: ...61 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS...
Страница 64: ...62 APPENDIX A STATUS SCREENS...
Страница 65: ...63 APPENDIX A STATUS SCREENS...
Страница 66: ...64 APPENDIX B USER MENU APPENDIX B USER MENU...
Страница 67: ...65 APPENDIX B USER MENU...
Страница 68: ...66 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU...
Страница 69: ...67 APPENDIX C INSTALLER MENU...
Страница 70: ...68 APPENDIX C INSTALLER MENU...
Страница 71: ...69 APPENDIX C INSTALLER MENU...