49
“A”
CODE
Error Display
Internal
No.
Error Description
Corrective Action
A12
SOFTWARE OUT OF DATE
E2PROM OUT OF DATE
10
Contents of e2prom is not
up-to-date.
Replace Control
A13
INTERNAL ERROR
13
Internal Software Error
Replace Control
A14
INTERNAL ERROR
14
Internal Software Error
Replace Control
A15
INTERNAL ERROR
16
Internal Software Error
Replace Control
A16
INTERNAL ERROR
22
Internal Software Error
Replace Control
A18
INTERNAL ERROR
19
Internal Software Error
Replace Control
A19
FALSE FLAME DETECTED
AFTER SHUTDOWN
20
Flame signal detected 10 sec.
after closing the gas valve.
1. Check flame sensor to be sure there is no short to
ground.
2. Check igniter to be sure there is not short to
ground.
3. This could also indicate that the gas valve doesn’t
close completely.
A20
FALSE FLAME DETECTED
BEFORE IGNITION
21
Flame signal detected before gas
valve opened.
4. Check flame sensor to be sure there is no short to
ground.
Check igniter to be sure there is not short to
ground.
A23
FLOW_SW_NOT_OPEN
25
CH flow switch not working.
1. Check for electrical continuity between wires
connected to terminals 9 & 10 from field supplied
flow switch.
2. If there is continuity when the pump is off, there is
a system piping or pump control
problem.
A24
FLOW_SW_NOT_CLOSED
26
CH flow switch not working.
1. Check for electrical continuity between wires
connected to terminals 9 & 10 from the field
supplied flow switch.
2. If there is no continuity, check to be sure the
pump is working.
3. If the pump is working correctly, check the
flow switch.
A33
FAN SPEED ERROR
8
Fan speed detected is more than
300 rpm different from targeted
value for more than 60 seconds.
1. Is the fan running at full speed?
• Check 4 wire control connection to blower
and control.
• Replace harness.
2. Is the fan running at a modulated speed?
• Check 4 wire control connection to blower
and control.
• Replace harness.
3. Is the fan not running?
• Check the 3 wire power connection to the
blower and control.
• Replace harness.
• Replace Blower.
A50
RETURN HIGHER THAN
SUPPLY
11
Boiler return water temperature
higher than supply for more than
5 ignition attempts.
1. Check system piping. Assure that the water is
entering the return connection and exiting the
supply connection.
2. Compare the supply thermistor reading to the
temperature gauge, if they don’t agree, replace the
supply thermistor.
Table 10.2 (cont’d): Control Board Locking Error Codes (manual reset):
TROUBLESHOOTING
Содержание PUREFIRE PFW-199
Страница 20: ...18 WATER PIPING AND CONTROLS Figure 4 3 Schematic Piping One Boiler with a Single Storage Tank...
Страница 21: ...19 WATER PIPING AND CONTROLS Figure 4 4 Schematic Piping One Boiler with Multiple Storage Tanks...
Страница 22: ...20 Figure 4 5 Schematic Piping Two Boilers with a Single Storage Tank WATER PIPING AND CONTROLS...
Страница 23: ...21 WATER PIPING AND CONTROLS Figure 4 6 Schematic Piping Two Boilers with Multiple Storage Tanks...
Страница 24: ...22 WATER PIPING AND CONTROLS Figure 4 7 Schematic Piping Alternate Piping with Patented Anti Scale System...
Страница 33: ...31 Figure 7 3 Internal Wiring Schematic for PFW 199 PFW 210 PFW 399 Boilers ELECTRICAL CONNECTIONS...
Страница 47: ...E LIGHTING OPERATING PROCEDURES 45 Figure 9 4 Lighting Operating Instructions START UP PROCEDURE...
Страница 60: ...58 Figure 13 2 Heat Exchanger Burner Assembly Repair Parts REPAIR PARTS...
Страница 63: ...61 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS...
Страница 64: ...62 APPENDIX A STATUS SCREENS...
Страница 65: ...63 APPENDIX A STATUS SCREENS...
Страница 66: ...64 APPENDIX B USER MENU APPENDIX B USER MENU...
Страница 67: ...65 APPENDIX B USER MENU...
Страница 68: ...66 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU...
Страница 69: ...67 APPENDIX C INSTALLER MENU...
Страница 70: ...68 APPENDIX C INSTALLER MENU...
Страница 71: ...69 APPENDIX C INSTALLER MENU...