17
WATER PIPING AND CONTROLS
c. The boiler pressure drop for various flow rates can
be determined using Figure 4.2, the Infinite
Energy Boiler Pump Sizing Graph.
d. Table 4.4 provides the flow rate and pressure drop
information that corresponds to 20°F temperature
rise (
Δ
T). The pressure drop shown is for the
boiler only. If there is significant system pressure
drop in the circulation system between the boiler
and the tank, this should be included when
specifying pumps.
e. Table 4.5 provides a list of recommended pumps
for PureFire hot water supply boilers.
* Pumps must be bronze fitted for potable water application
D. SYSTEM PIPING
1. Figure 4.3 shows piping for a single boiler with a
single storage tank. When using the factory specified
pump, the maximum total pipe length is 30 feet (10
meters) with 6 90° elbows all at the full pipe diameter
of the pump connections.
2. In Figure 4.4, a single boiler is used with multiple
water storage tanks. The pumps are piped in parallel
with reverse return piping.
3. Figure 4.5 shows two boilers piped into a single
storage tank.
4. Figure 4.6 shows piping for two boilers and two water
storage tanks.
5. In Figure 4.7, we show a single boiler with a single
tank using a patented anti-scale principle. In this
configuration, the boiler control switches the 3-way
valve to bypass when the call for heat ends. The
pump is then operated to draw cool water from the
anti-scale buffer tank until the supply and return
temperatures equalize.
6. In Figure 4.8, a plate heat exchanger is used to isolate
the boiler from the domestic hot water supply system.
This strategy can be used if the domestic water does
not meet the water quality guidelines presented earlier
in this section. Note that a hydronic thermal
expansion tank is required in this closed-loop system.
Table 4.5: Table 4.5: Pump Selection Chart
(20°F
Δ
T)
Pump
Manufacturer
PFW-199
PFW-210
PFW-399
Bell & Gossett
PL-36
PL-36
PL-55
Grundfos
UPS32-80F
Medium Speed
UPS32-80F
Medium Speed
UPS32-160F
Medium Speed
Taco
1400-20
1400-20
1400-50
Table 4.4: Flow Rate and Pressure Drop for Various
System Temperature Rise Values
Flow Rate vs Pressure Drop at 20°F
PFW-199
PFW-210
PFW-399
GPM
(LPM)
Feet (m)
GPM
(LPM)
Feet (m)
GPM
(LPM)
Feet (m)
18.3 (69.3) 17.3 (5.3) 19.3 (73.1) 18.8 (5.7) 37.3 (141.2) 18.1 (5.5)
Содержание PUREFIRE PFW-199
Страница 20: ...18 WATER PIPING AND CONTROLS Figure 4 3 Schematic Piping One Boiler with a Single Storage Tank...
Страница 21: ...19 WATER PIPING AND CONTROLS Figure 4 4 Schematic Piping One Boiler with Multiple Storage Tanks...
Страница 22: ...20 Figure 4 5 Schematic Piping Two Boilers with a Single Storage Tank WATER PIPING AND CONTROLS...
Страница 23: ...21 WATER PIPING AND CONTROLS Figure 4 6 Schematic Piping Two Boilers with Multiple Storage Tanks...
Страница 24: ...22 WATER PIPING AND CONTROLS Figure 4 7 Schematic Piping Alternate Piping with Patented Anti Scale System...
Страница 33: ...31 Figure 7 3 Internal Wiring Schematic for PFW 199 PFW 210 PFW 399 Boilers ELECTRICAL CONNECTIONS...
Страница 47: ...E LIGHTING OPERATING PROCEDURES 45 Figure 9 4 Lighting Operating Instructions START UP PROCEDURE...
Страница 60: ...58 Figure 13 2 Heat Exchanger Burner Assembly Repair Parts REPAIR PARTS...
Страница 63: ...61 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS...
Страница 64: ...62 APPENDIX A STATUS SCREENS...
Страница 65: ...63 APPENDIX A STATUS SCREENS...
Страница 66: ...64 APPENDIX B USER MENU APPENDIX B USER MENU...
Страница 67: ...65 APPENDIX B USER MENU...
Страница 68: ...66 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU...
Страница 69: ...67 APPENDIX C INSTALLER MENU...
Страница 70: ...68 APPENDIX C INSTALLER MENU...
Страница 71: ...69 APPENDIX C INSTALLER MENU...