e. Additional Safety Functions:
• The installer can choose between a low water
cut-off (LWCO) or a flow switch to prevent
firing of the boiler without sufficient water in
the system. Figure 8.39 shows the selection
screen for Additional Safety Functions.
• The control is shipped with LowWaterCO as a
default setting and includes a factory supplied
jumper that allows the boiler to operate if this
safety device is not installed. Table 8.8 shows
the available options for this parameter.
• If the boiler is set to flow switch, the control
first checks to assure that the circuit is open
before turning on the pump. Once the pump is
on, the control requires the flow switch circuit
to be closed.
• The system can accept both a LWCO and flow
switch as long as they are wired in series so
that the circuit opens when there is no flow in
the boiler.
f.
Blower Post Purge:
The installing contractor can increase the blower
post-purge time from the 30 second minimum up
to 120 seconds in 1 second increments. Figure
8.40 shows the Blower Post-purge Setting screen.
Table 8.9 shows the range of values for the Blower
Post-purge time. Keep in mind that increasing the
blower post-purge time can adversely affect the
efficiency of the boiler.
3.
Installer Menu - Service Notification
a. The IEW boiler allows the service technician to set
up notifications for routine maintenance. When
enabled, the notification can be set up on Hours
of Operation, Cycles, or on a pre-determined
date. When the notification criteria are met, the
screen shown in Figure 8.41 is displayed with
“SERVICE” flashing.
b. To reset the hour or cycle counters, press the
Select key on Screen #1 under Service
Notification shown in Figure 8.42.
c. Screen #2, shown in Figure 8.43, is used to set
the notification criteria. Table 8.10 shows the
choices for this parameter:
d. To set the number of hours until notification, press
the
Select
key while viewing Screen #3, shown
in Figure 8.44, and press the
Þ
and
Ý
keys to
change the number of hours in 100 hour
increments.
e. Similarly to set the number of cycles, press the
Select key while viewing Screen #4 shown in
Figure 8.45 and press the t and s keys to change
the number of cycles in 1000 cycle increments.
Figure 8.39: Additional Safety Functions Selection
B O I L E R
S E T T I N G S
7 ▲
A d d i t i o n a l
S a f e t y
F u n c t i o n s
L o w W a t e r C O
▼
Parameter
Default
Alternate
Additional Safety Functions
LowWaterCO
Flow Switch
Table 8.8: Additional Safety Function Values
Figure 8.40: Blower Post-purge Setting
B O I L E R
S E T T I N G S
8 ▲
B l o w e r
P o s t
P u r g e
T i m e
3 0 s e c ▼
Parameter
Minimum
Default
Maximum
Blower Post-purge Time
30 seconds
30 seconds
120 seconds
Table 8.9: Blower Post Purge Time Value Range
Figure 8.41: Service Notification Status
Figure 8.42: Reset Notification Time or Cycles
Figure 8.43: Notification Criteria
Criteria
Minimum
Default
Maximum
Off
Notification Disabled (Default)
HRS
0 HRS
4000 HRS
8000 HRS
CYCLES
0 CYC
50,000 CYC
20,000 CYC
DATE
Set Date, Month & Year
Table 8.10: Notification Criteria
Figure 8.44: Notification on Hours
Figure 8.45: Notification on Cycles
39
BOILER CONTROL: INTERNAL WIRING & OPERATION
Содержание PUREFIRE PFW-199
Страница 20: ...18 WATER PIPING AND CONTROLS Figure 4 3 Schematic Piping One Boiler with a Single Storage Tank...
Страница 21: ...19 WATER PIPING AND CONTROLS Figure 4 4 Schematic Piping One Boiler with Multiple Storage Tanks...
Страница 22: ...20 Figure 4 5 Schematic Piping Two Boilers with a Single Storage Tank WATER PIPING AND CONTROLS...
Страница 23: ...21 WATER PIPING AND CONTROLS Figure 4 6 Schematic Piping Two Boilers with Multiple Storage Tanks...
Страница 24: ...22 WATER PIPING AND CONTROLS Figure 4 7 Schematic Piping Alternate Piping with Patented Anti Scale System...
Страница 33: ...31 Figure 7 3 Internal Wiring Schematic for PFW 199 PFW 210 PFW 399 Boilers ELECTRICAL CONNECTIONS...
Страница 47: ...E LIGHTING OPERATING PROCEDURES 45 Figure 9 4 Lighting Operating Instructions START UP PROCEDURE...
Страница 60: ...58 Figure 13 2 Heat Exchanger Burner Assembly Repair Parts REPAIR PARTS...
Страница 63: ...61 APPENDIX A STATUS SCREENS APPENDIX A STATUS SCREENS...
Страница 64: ...62 APPENDIX A STATUS SCREENS...
Страница 65: ...63 APPENDIX A STATUS SCREENS...
Страница 66: ...64 APPENDIX B USER MENU APPENDIX B USER MENU...
Страница 67: ...65 APPENDIX B USER MENU...
Страница 68: ...66 APPENDIX C INSTALLER MENU APPENDIX C INSTALLER MENU...
Страница 69: ...67 APPENDIX C INSTALLER MENU...
Страница 70: ...68 APPENDIX C INSTALLER MENU...
Страница 71: ...69 APPENDIX C INSTALLER MENU...