background image

PEAK® IOM57 Input/Output Modules Installation Instructions

12

Analog

(outputs)

(IOM5731)

OUT

n

Analog output - Voltage mode (0 VDC–10 VDC)

10 VDC maximum output voltage
10 mA maximum output current
Requires an external load of 1,000 ohm or more.

Note:

 The AO operates in the Voltage mode when it is 

connected to devices with impedances greater then 1,000 

ohm. Devices that drop below 1,000 ohm may not operate 

as intended for Voltage mode applications.

See guideline

 

A in Table 5

.

OCOM

n

AO common
Note: 

All analog OCOM

terminals share a common, 

which is not isolated from all other commons.

Same as OUT

RELAY

(outputs)

(IOM5731)

OUT NO

n

Normal open contact

Connects OCOM to OUT NO when activated.

UL Listed

1/4 hp 120 VAC, 1/2 hp 240 VAC
360 VA Pilot Duty at 120/240 VAC (B300)
3 A Non-inductive 24 VAC–240 VAC

CE Marking

24 VAC, 6 (4) amperes N.O. or N.C. only, SELV

CE Marking

6 (4) A N.O. or N.C. only, 240 VAC

The relay output terminals 

can accommodate the 

following maximum wire 

sizes:
Two wires per terminal:
1.5 mm

2

 (16 AWG) 

maximum wire size

or

One wire per terminal:
2.5 mm

2

 (12 AWG) 

maximum

Note:

 You must determine 

the required wire size for the 

high-voltage (>30 V) 

terminals according to relay 

ratings, the applied load, and 

the local, national, or regional 

electrical codes.

OCOM

n

Relay common

Isolated from all other terminal commons, including other 

Relay Commons.

OUT NC

n

Normal closed contact

Connects OCOM to OUT NC when not activated.

UL Listed

1/4 hp 120 VAC, 1/2 hp 240 VAC
360 VA Pilot Duty at 120/240 VAC (B300)
3 A Non-inductive 24–240 VAC

CE Marking

6 (4) A N.O. or N.C. only, 240 VAC

Note:

OUT1 through OUT4 and OUT5 through OUT8 are 

groups that must be powered by compatible voltage levels. 

Isolation insulation exists within the two groups. For 

example, 24 V I/O can connect to OUT1 through OUT4, 

and high voltage I/O can connect to OUT5 through OUT8.

Note:

You cannot mix voltage levels within the 

groups.

Table 4:  IOM terminal blocks, functions, ratings, requirements, and cables (Part 2 of 2)

Terminal block 
label

Terminal 
label

Function, ratings, requirements

Determine wire size and 
maximum cable length

Содержание PEAK IOM57

Страница 1: ...the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver to secure wires in the te...

Страница 2: ...her devices or wiring can interfere with controller communication Observe these additional guidelines when you mount a field controller in a panel or enclosure Mount the controller so that the enclosu...

Страница 3: ...ole locations on the wall or surface Alternatively hold the controller up to the wall or surface in the proper mounting position and mark the hole locations through the mounting clips 3 Drill holes in...

Страница 4: ...IOM5711 physical features Callout Physical feature Description and references 1 Device address DIP Switch Block 2 Mounting clip 3 24 VAC Class 2 supply power terminal block 4 Cover lift tab 5 SA bus...

Страница 5: ...imentation avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des compo...

Страница 6: ...The SA bus supervisor advanced application field equipment controller FAC field equipment controller FEC or VAV modular assembly VMA supplies 15 VDC to devices on the SA bus that require power SA FC b...

Страница 7: ...instructions and project installation drawings for wiring details IMPORTANT Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across th...

Страница 8: ...set to the correct device address See Setting the device addresses 3 Set DIP switch 128 to ON enables wireless operation on the controller For more information about installing a controller in a wire...

Страница 9: ...powered UI Current input external source isolated UI Current input internal source 2 wire UI Current input internal source 3 wire UI Current input external source in loop UI Table 3 Termination detai...

Страница 10: ...nstructions 10 Feedback from EPP 1000 UI Dry contact UI Dry contact UO Voltage analog output AO 0 10 VDC output to actuator internal source UO Table 3 Termination details Part 3 of 3 Type of field dev...

Страница 11: ...irements and cables Part 1 of 2 Terminal block label Terminal label Function ratings requirements Determine wire size and maximum cable length UNIVERSAL inputs IOM5711 15 V 15 VDC power source for act...

Страница 12: ...owing maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum wire size or One wire per terminal 2 5 mm2 12 AWG maximum Note You must determine the required wire size for the high voltage 30...

Страница 13: ...maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297...

Страница 14: ...rminal blocks functions ratings requirements and cables Terminal block port label Terminal labels Function electrical ratings and requirements Recommended cable type1 1 See Table 5 to determine wire s...

Страница 15: ...FR1800 Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure that switch 128 is set to OFF Note Do not connect a controller with switch 128 set to ON to an active...

Страница 16: ...ch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note PEA...

Страница 17: ...be set as a terminating device on the bus Note The EOL termination rules for SA buses and FC buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed info...

Страница 18: ...D states LED label LED color Normal LED state Description of LED state POWER Green On steady Off steady No supply power or the controller s polyswitch resettable fuse is open Check output wiring for s...

Страница 19: ...ry outputs BOs or configurable outputs COs Ambient conditions Operating 40 C to 70 C 40 F to 158 F 10 to 90 RH noncondensing Storage 40 C to 80 C 40 F to 176 F 5 to 95 RH noncondensing Addressing DIP...

Страница 20: ...A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that these products are in compliance with the essen...

Страница 21: ...Modules Installation Instructions 21 PEAK and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Build...

Отзывы: