PEAK® IOM57 Input/Output Modules Installation Instructions

5

Wiring   

 

For detailed information on configuring and wiring an MS/TP bus, FC bus, and SA bus, refer to the 

MS/TP 

Communications Bus Technical Bulletin (LIT-12011034).

Terminal blocks and bus ports

See Figure 2 for terminal block and bus port locations on the controller. Observe the following guidelines when 
wiring a controller.

Input and output terminal blocks

Most of the input terminal blocks are mounted on the bottom of the controller and the output terminal blocks are 
mounted on the top of the controller. See Table 4 for more information about I/O terminal functions, requirements, 
and ratings.

Risk of Electric Shock.

Disconnect or isolate all power supplies before making electrical connections. More than one disconnection or 
isolation may be required to completely de-energize equipment. Contact with components carrying hazardous 
voltage can cause electric shock and may result in severe personal injury or death.

Risque de décharge électrique.

Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique. Plusieurs isolations et 
débranchements sont peut-être nécessaires pour -couper entièrement l'alimentation de l'équipement. Tout contact 
avec des composants conducteurs de tensions dangereuses risque d'entraîner une décharge électrique et de 
provoquer des blessures graves, voire mortelles.

Risk of Property Damage.

Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected 
wires may result in permanent damage to the equipment.

Risque de dégâts matériels.

Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un 
court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.

IMPORTANT:

Do not exceed the controller electrical ratings. Exceeding controller electrical ratings can result in 

permanent damage to the controller and void any warranty.

IMPORTANT:

Use copper conductors only. Make all wiring in accordance with local, national, and regional 

regulations.

IMPORTANT:

Electrostatic discharge can damage controller components. Use proper electrostatic discharge 

precautions during installation, setup, and servicing to avoid damaging the controller.

Содержание PEAK IOM57

Страница 1: ...the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver to secure wires in the te...

Страница 2: ...her devices or wiring can interfere with controller communication Observe these additional guidelines when you mount a field controller in a panel or enclosure Mount the controller so that the enclosu...

Страница 3: ...ole locations on the wall or surface Alternatively hold the controller up to the wall or surface in the proper mounting position and mark the hole locations through the mounting clips 3 Drill holes in...

Страница 4: ...IOM5711 physical features Callout Physical feature Description and references 1 Device address DIP Switch Block 2 Mounting clip 3 24 VAC Class 2 supply power terminal block 4 Cover lift tab 5 SA bus...

Страница 5: ...imentation avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des compo...

Страница 6: ...The SA bus supervisor advanced application field equipment controller FAC field equipment controller FEC or VAV modular assembly VMA supplies 15 VDC to devices on the SA bus that require power SA FC b...

Страница 7: ...instructions and project installation drawings for wiring details IMPORTANT Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across th...

Страница 8: ...set to the correct device address See Setting the device addresses 3 Set DIP switch 128 to ON enables wireless operation on the controller For more information about installing a controller in a wire...

Страница 9: ...powered UI Current input external source isolated UI Current input internal source 2 wire UI Current input internal source 3 wire UI Current input external source in loop UI Table 3 Termination detai...

Страница 10: ...nstructions 10 Feedback from EPP 1000 UI Dry contact UI Dry contact UO Voltage analog output AO 0 10 VDC output to actuator internal source UO Table 3 Termination details Part 3 of 3 Type of field dev...

Страница 11: ...irements and cables Part 1 of 2 Terminal block label Terminal label Function ratings requirements Determine wire size and maximum cable length UNIVERSAL inputs IOM5711 15 V 15 VDC power source for act...

Страница 12: ...owing maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum wire size or One wire per terminal 2 5 mm2 12 AWG maximum Note You must determine the required wire size for the high voltage 30...

Страница 13: ...maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297...

Страница 14: ...rminal blocks functions ratings requirements and cables Terminal block port label Terminal labels Function electrical ratings and requirements Recommended cable type1 1 See Table 5 to determine wire s...

Страница 15: ...FR1800 Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure that switch 128 is set to OFF Note Do not connect a controller with switch 128 set to ON to an active...

Страница 16: ...ch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note PEA...

Страница 17: ...be set as a terminating device on the bus Note The EOL termination rules for SA buses and FC buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed info...

Страница 18: ...D states LED label LED color Normal LED state Description of LED state POWER Green On steady Off steady No supply power or the controller s polyswitch resettable fuse is open Check output wiring for s...

Страница 19: ...ry outputs BOs or configurable outputs COs Ambient conditions Operating 40 C to 70 C 40 F to 158 F 10 to 90 RH noncondensing Storage 40 C to 80 C 40 F to 176 F 5 to 95 RH noncondensing Addressing DIP...

Страница 20: ...A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that these products are in compliance with the essen...

Страница 21: ...Modules Installation Instructions 21 PEAK and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Build...

Отзывы: