PEAK® IOM57 Input/Output Modules Installation Instructions
3
4. To secure the controller on the DIN rail, push the bottom mounting clip in and up.
To remove the controller from the DIN rail, pull the bottom mounting clip out to the extended position and
carefully lift the controller off the DIN rail.
Wall mount applications
To mount a field controller directly on a wall or other flat vertical surface, complete the following steps:
1. Pull the bottom mounting clip outward and ensure that it is locked in the extended position, as shown in
2. Position the controller in the proper mounting position shown in Figure 2 and mark the mounting hole locations
on the wall or surface. Alternatively, hold the controller up to the wall or surface in the proper mounting position
and mark the hole locations through the mounting clips.
3. Drill holes in the wall or surface at the marked locations, and insert appropriate wall anchors in the holes if
necessary.
4. Hold the controller in place, and insert the screws through the mounting clips and into the holes or wall
anchors. Carefully tighten all of the screws.
IMPORTANT:
Do not overtighten the mounting screws. Overtightening the screws may damage the mounting
clips.
Table 1: PEAK IOM5731 physical features (Part 1 of 2)
Callout
Physical feature: description and references
1
Device address DIP switch block
2
Mounting clip
3
24 VAC, Class 2 supply power terminal block
4
Cover lift tab
Figure 2: PEAK IOM5711 physical features
1
2
2
3
4
4
5
8
9
6
6
7