background image

PEAK® IOM57 Input/Output Modules Installation Instructions

20

Mounting

Screw mount on flat surface with three integral mounting clips on controller or horizontally 

mounted on single 35 mm DIN rail mount (preferred) inside a supplementary enclosure 

minimum IP20 rating that only qualified personnel can access.

Housing

Enclosure material: ABS and polycarbonate UL94 5VB; self extinguishing, Plenum-Rated
Protection Class: IP20 (IEC529)

Dimensions 

(Height x Width x Depth)

IOM5711: 

146 mm x 165 mm x 56 mm (5-3/4 in. x 6-1/2 in. x 2-1/4 in.) including terminals 

and mounting clips

IOM5731:

 146 mm x 190 mm x 61 mm (5-3/4 in. x 7-1/2 in. x 2-3/8 in.) including terminals 

and mounting clips

Note: 

Mounting space requires an additional 50 mm (2 in.) space on top, bottom and front 

face of controller for easy cover removal, ventilation and wire terminations.

Weight

0.5 kg (1.1 lb) maximum

Compliance

United States:

 UL Listed, File E107041, CCN PAZX, UL 916; FCC Compliant to CFR47, 

Part 15, Subpart B, Class A

Canada:

 UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal 

Equipment; Industry Canada Compliant, ICES-003

Europe:

 Johnson Controls declares that these products are in compliance with the 

essential requirements and other relevant provisions of the EMC Directive and Low Voltage 

Directive. Declared as Independently Mounted, Intended for Panel Mounting, Operating 

Control Type 1.B, 4kV rated impulse voltage, 100.7°C ball pressure test.

Australia and New Zealand: 

RCM Mark, Australia/NZ Emissions Compliant

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond 

these specifications, consult the local Johnson Controls® office. Johnson Controls shall not be liable for damages resulting from 

misapplication or misuse of its products.

European Single Point of Contact:

NA/SA Single Point of Contact:

APAC Single Point of Contact:

JOHNSON CONTROLS

WESTENDHOF 3

45143 ESSEN

GERMANY

JOHNSON CONTROLS

507 E MICHIGAN ST

MILWAUKEE WI 53202

USA

JOHNSON CONTROLS

C/O CONTROLS PRODUCT MANAGEMENT

NO. 22 BLOCK D NEW DISTRICT

WUXI JIANGSU PROVINCE 214142

CHINA

PEAK IOM57 Series technical specifications (Part 2 of 2 )

Содержание PEAK IOM57

Страница 1: ...the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver to secure wires in the te...

Страница 2: ...her devices or wiring can interfere with controller communication Observe these additional guidelines when you mount a field controller in a panel or enclosure Mount the controller so that the enclosu...

Страница 3: ...ole locations on the wall or surface Alternatively hold the controller up to the wall or surface in the proper mounting position and mark the hole locations through the mounting clips 3 Drill holes in...

Страница 4: ...IOM5711 physical features Callout Physical feature Description and references 1 Device address DIP Switch Block 2 Mounting clip 3 24 VAC Class 2 supply power terminal block 4 Cover lift tab 5 SA bus...

Страница 5: ...imentation avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des compo...

Страница 6: ...The SA bus supervisor advanced application field equipment controller FAC field equipment controller FEC or VAV modular assembly VMA supplies 15 VDC to devices on the SA bus that require power SA FC b...

Страница 7: ...instructions and project installation drawings for wiring details IMPORTANT Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across th...

Страница 8: ...set to the correct device address See Setting the device addresses 3 Set DIP switch 128 to ON enables wireless operation on the controller For more information about installing a controller in a wire...

Страница 9: ...powered UI Current input external source isolated UI Current input internal source 2 wire UI Current input internal source 3 wire UI Current input external source in loop UI Table 3 Termination detai...

Страница 10: ...nstructions 10 Feedback from EPP 1000 UI Dry contact UI Dry contact UO Voltage analog output AO 0 10 VDC output to actuator internal source UO Table 3 Termination details Part 3 of 3 Type of field dev...

Страница 11: ...irements and cables Part 1 of 2 Terminal block label Terminal label Function ratings requirements Determine wire size and maximum cable length UNIVERSAL inputs IOM5711 15 V 15 VDC power source for act...

Страница 12: ...owing maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum wire size or One wire per terminal 2 5 mm2 12 AWG maximum Note You must determine the required wire size for the high voltage 30...

Страница 13: ...maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297...

Страница 14: ...rminal blocks functions ratings requirements and cables Terminal block port label Terminal labels Function electrical ratings and requirements Recommended cable type1 1 See Table 5 to determine wire s...

Страница 15: ...FR1800 Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure that switch 128 is set to OFF Note Do not connect a controller with switch 128 set to ON to an active...

Страница 16: ...ch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note PEA...

Страница 17: ...be set as a terminating device on the bus Note The EOL termination rules for SA buses and FC buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed info...

Страница 18: ...D states LED label LED color Normal LED state Description of LED state POWER Green On steady Off steady No supply power or the controller s polyswitch resettable fuse is open Check output wiring for s...

Страница 19: ...ry outputs BOs or configurable outputs COs Ambient conditions Operating 40 C to 70 C 40 F to 158 F 10 to 90 RH noncondensing Storage 40 C to 80 C 40 F to 176 F 5 to 95 RH noncondensing Addressing DIP...

Страница 20: ...A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that these products are in compliance with the essen...

Страница 21: ...Modules Installation Instructions 21 PEAK and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Build...

Отзывы: