PEAK® IOM57 Input/Output Modules Installation Instructions

18

Commissioning the controllers

Commission controllers with the Controller Configuration Tool (CCT) software, either using a Wireless 
Commissioning Converter, a ZigBee wireless dongle, or a BACnet router mode when connected to an NAE or 
NCE. Refer to the 

Controller Tool Help (LIT-12011147)

 for detailed information on commissioning controllers.

Hands-Off-Auto (HOA) relay operation for IOM5731

Each relay has a normally closed, normally open, and common connection. Each output has an On-Auto-Off slide 
switch that provides a manual override to the respective relay output. Set the IOM5731 to Auto for normal 
functionality. A multicolor LED appears near each relay that indicates if the output is On or in Override. Table 9 
describes the LED indicators.

Troubleshooting the controllers

Observe the status LEDs on the front of the controller and see Table 9 to troubleshoot the controller.

Repair information

If a controller fails to operate within its specifications, replace the controller. For a replacement controller, contact 
your Johnson Controls representative.

Accessories

See the following table for controller accessories ordering information.

Table 9:  Status LEDs and descriptions of LED states

LED label

LED color

Normal LED 
state

Description of LED state

POWER

Green

On steady

Off steady = No supply power or the controller’s polyswitch/resettable fuse is 

open. Check output wiring for short circuits and cycle power to controller. 
On steady = Power connected

FAULT

Red

Off steady

Off steady = No faults
On steady = Device fault; no application loaded; Main code download 

required, if controller is in Boot mode, or a firmware mismatch exists between 

the controller and the ZFR1811 Wireless Field Bus Router.
Blink - 2 Hz = Download or Startup in progress, not ready for normal 

operation

SA/FC BUS

Green

Blink - 2 Hz

Blink - 2 Hz = Data transmission (normal communication)
Off Steady = No data transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring

EOL

Amber

Off (Except on 

terminating 

devices)

On steady = EOL switch in ON position
Off steady = EOL switch in Off position

RELAY

Amber, 

Green

On steady 

green 
Off steady

On steady green = Relay switch is set to AUTO, and relay output is active ON
On steady amber = Relay switch is set to OVERRIDE ON, and relay output is 

active ON
Off steady = Relay switch is set to either AUTO or OFF and relay output is 

OFF

Table 10:  Accessories ordering information (Part 1 of 2)

Product code number

Description

MS-BTCVT-1

Bluetooth® Wireless Commissioning Converter

MS-ZFR1811-0

Wireless Field Bus Router

TP-2420

Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug

Содержание PEAK IOM57

Страница 1: ...the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver to secure wires in the te...

Страница 2: ...her devices or wiring can interfere with controller communication Observe these additional guidelines when you mount a field controller in a panel or enclosure Mount the controller so that the enclosu...

Страница 3: ...ole locations on the wall or surface Alternatively hold the controller up to the wall or surface in the proper mounting position and mark the hole locations through the mounting clips 3 Drill holes in...

Страница 4: ...IOM5711 physical features Callout Physical feature Description and references 1 Device address DIP Switch Block 2 Mounting clip 3 24 VAC Class 2 supply power terminal block 4 Cover lift tab 5 SA bus...

Страница 5: ...imentation avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des compo...

Страница 6: ...The SA bus supervisor advanced application field equipment controller FAC field equipment controller FEC or VAV modular assembly VMA supplies 15 VDC to devices on the SA bus that require power SA FC b...

Страница 7: ...instructions and project installation drawings for wiring details IMPORTANT Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across th...

Страница 8: ...set to the correct device address See Setting the device addresses 3 Set DIP switch 128 to ON enables wireless operation on the controller For more information about installing a controller in a wire...

Страница 9: ...powered UI Current input external source isolated UI Current input internal source 2 wire UI Current input internal source 3 wire UI Current input external source in loop UI Table 3 Termination detai...

Страница 10: ...nstructions 10 Feedback from EPP 1000 UI Dry contact UI Dry contact UO Voltage analog output AO 0 10 VDC output to actuator internal source UO Table 3 Termination details Part 3 of 3 Type of field dev...

Страница 11: ...irements and cables Part 1 of 2 Terminal block label Terminal label Function ratings requirements Determine wire size and maximum cable length UNIVERSAL inputs IOM5711 15 V 15 VDC power source for act...

Страница 12: ...owing maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum wire size or One wire per terminal 2 5 mm2 12 AWG maximum Note You must determine the required wire size for the high voltage 30...

Страница 13: ...maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297...

Страница 14: ...rminal blocks functions ratings requirements and cables Terminal block port label Terminal labels Function electrical ratings and requirements Recommended cable type1 1 See Table 5 to determine wire s...

Страница 15: ...FR1800 Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure that switch 128 is set to OFF Note Do not connect a controller with switch 128 set to ON to an active...

Страница 16: ...ch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note PEA...

Страница 17: ...be set as a terminating device on the bus Note The EOL termination rules for SA buses and FC buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed info...

Страница 18: ...D states LED label LED color Normal LED state Description of LED state POWER Green On steady Off steady No supply power or the controller s polyswitch resettable fuse is open Check output wiring for s...

Страница 19: ...ry outputs BOs or configurable outputs COs Ambient conditions Operating 40 C to 70 C 40 F to 158 F 10 to 90 RH noncondensing Storage 40 C to 80 C 40 F to 176 F 5 to 95 RH noncondensing Addressing DIP...

Страница 20: ...A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that these products are in compliance with the essen...

Страница 21: ...Modules Installation Instructions 21 PEAK and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Build...

Отзывы: