background image

PEAK® IOM57 Input/Output Modules Installation Instructions

15

The DIP switch block has eight switches, numbered 128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1 are 
device address switches. Switch 128 is a mode switch that enables a controller to operate on a ZFR1800 Series 
Wireless Field Bus. Switch 128 must be set to OFF for all hard-wired SA and FC bus applications. Set switch 128 
to ON for wireless FC bus applications only.

Note:

PEAK field controllers ship with switch 128 ON and the remaining address switches off; this renders the 

controllers wired subordinate devices, which do not operate on MS/TP buses, but will not interfere with bus 
operation. Set a valid and unique device address on the controller before you apply power to the controller on the 
bus.

To set the device addresses on PEAK field controllers, complete the following steps:

1. Set all of the switches on the address DIP switch block (128 through 1) to OFF. 

2. Set one or more of the seven address switches (64 through 1) to ON, so that the sum of the switch numbers 

set to ON equals the intended device address. See Table  for valid device addresses.

Set the highest number switch that is less than or equal to the intended device address to ON. Continue to set 
lower numbered switches until the total equals the intended address. For example, if the intended device 
address is 21, set switch 16 to ON first, then set switch 4 to ON, followed by switch 1 (16+4+1= 21).

3. Set switch 128 to ON only for controllers on a ZFR1800 Series Wireless Field Bus application. For all hard-

wired SA and FC bus applications, ensure that switch 128 is set to OFF.

Note:

Do not connect a controller with switch 128 set to ON to an active (hard-wired) SA or FC bus. When a 

controller with switch 128 is set to ON and a device address from 4 to 127 is connected to a wired field bus, the 
entire field bus is rendered inoperable until the controller is disconnected or switch 128 is set to OFF.

Refer to the 

ZFR1800 Series Wireless Field Bus System Technical Bulletin (LIT-12011295) 

for more information on 

device addresses in wireless applications.

4. Set a unique and sequential device address for each of the controllers connected on the SA or FC bus starting 

with device address 4.

To ensure the best bus performance, set sequential device addresses with no gaps in the device address 
range (4, 5, 6, 7, 8, 9, and so on). You do not need to physically connect the controllers on the bus in their 
numerical device address order.

5. Write each controller's device address on the white label below the DIP switch block on the controller's cover.

The following table describes the FC bus and SA bus devices addresses for Johnson Controls MS/TP 
communications bus applications.

Table 7: SA/FC bus device address descriptions (Part 1 of 2)

Device address

Use on description

0

(Switch 128 Off)

Reserved for FC bus supervisory controller (not for use on controllers).

1 to 3

(Switch 128 Off)

Reserved for peripheral devices (not for use on controllers).

Figure 9:  Device address DIP switch block set 

to address 21

1

2

8

6

4

3

2

1

6

8

4

2

1

ON

Note:

 Switch 128 is used to

enable or disable a controller
for wireless operation.

F

IG:

fe

c_

ad

dr

es

s_

di

p_

sw

itc

h

Содержание PEAK IOM57

Страница 1: ...the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver to secure wires in the te...

Страница 2: ...her devices or wiring can interfere with controller communication Observe these additional guidelines when you mount a field controller in a panel or enclosure Mount the controller so that the enclosu...

Страница 3: ...ole locations on the wall or surface Alternatively hold the controller up to the wall or surface in the proper mounting position and mark the hole locations through the mounting clips 3 Drill holes in...

Страница 4: ...IOM5711 physical features Callout Physical feature Description and references 1 Device address DIP Switch Block 2 Mounting clip 3 24 VAC Class 2 supply power terminal block 4 Cover lift tab 5 SA bus...

Страница 5: ...imentation avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des compo...

Страница 6: ...The SA bus supervisor advanced application field equipment controller FAC field equipment controller FEC or VAV modular assembly VMA supplies 15 VDC to devices on the SA bus that require power SA FC b...

Страница 7: ...instructions and project installation drawings for wiring details IMPORTANT Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across th...

Страница 8: ...set to the correct device address See Setting the device addresses 3 Set DIP switch 128 to ON enables wireless operation on the controller For more information about installing a controller in a wire...

Страница 9: ...powered UI Current input external source isolated UI Current input internal source 2 wire UI Current input internal source 3 wire UI Current input external source in loop UI Table 3 Termination detai...

Страница 10: ...nstructions 10 Feedback from EPP 1000 UI Dry contact UI Dry contact UO Voltage analog output AO 0 10 VDC output to actuator internal source UO Table 3 Termination details Part 3 of 3 Type of field dev...

Страница 11: ...irements and cables Part 1 of 2 Terminal block label Terminal label Function ratings requirements Determine wire size and maximum cable length UNIVERSAL inputs IOM5711 15 V 15 VDC power source for act...

Страница 12: ...owing maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum wire size or One wire per terminal 2 5 mm2 12 AWG maximum Note You must determine the required wire size for the high voltage 30...

Страница 13: ...maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297...

Страница 14: ...rminal blocks functions ratings requirements and cables Terminal block port label Terminal labels Function electrical ratings and requirements Recommended cable type1 1 See Table 5 to determine wire s...

Страница 15: ...FR1800 Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure that switch 128 is set to OFF Note Do not connect a controller with switch 128 set to ON to an active...

Страница 16: ...ch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note PEA...

Страница 17: ...be set as a terminating device on the bus Note The EOL termination rules for SA buses and FC buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed info...

Страница 18: ...D states LED label LED color Normal LED state Description of LED state POWER Green On steady Off steady No supply power or the controller s polyswitch resettable fuse is open Check output wiring for s...

Страница 19: ...ry outputs BOs or configurable outputs COs Ambient conditions Operating 40 C to 70 C 40 F to 158 F 10 to 90 RH noncondensing Storage 40 C to 80 C 40 F to 176 F 5 to 95 RH noncondensing Addressing DIP...

Страница 20: ...A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that these products are in compliance with the essen...

Страница 21: ...Modules Installation Instructions 21 PEAK and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Build...

Отзывы: