PEAK® IOM57 Input/Output Modules Installation Instructions

11

Terminal wiring guidelines, functions, ratings, and requirements

Input and output wiring guidelines

Table 4 provides information and guidelines about the functions, ratings, and requirements for the controller input 
and output terminals; and references guidelines for determining proper wire sizes and cable lengths.

In addition to the wiring guidelines in Table 4, observe the following guidelines when you wire controller inputs and 
outputs:

Run all low-voltage wiring and cables separately from high-voltage wiring.

All input and output cables, regardless of wire size or number of wires, should consist of stranded, insulated, 
and twisted copper wires. 

You do not need shielded cable for input or output cables.

It is best practice to use shielded cable for input and output cables that are exposed to high electromagnetic or 
radio frequency noise.

Inputs and outputs with cables less than 30 m (100 ft) typically do not require an offset in the software setup. 
Cable runs over 30 m (100 ft) may require an offset in the input/output software setup. 

Table 4:  IOM terminal blocks, functions, ratings, requirements, and cables (Part 1 of 2)

Terminal block 
label

Terminal 
label

Function, ratings, requirements

Determine wire size and 
maximum cable length

UNIVERSAL

(inputs)

(IOM5711)

+ 15 V

15 VDC power source 

for active (3-wire) input devices 

connected to the universal IN

n

 terminals.

Provides 200 mA total current

Same as (universal) IN

n

Note:

 Use 3-wire cable for 

devices that source power 

from the + 15 V terminal.

+ 5 V

5 VDC power source 

for active (3-wire) input devices 

connected to the universal IN

n

 terminals.

Provides 50 mA total current 

IN

n

Analog input - Voltage Mode (0 VDC–10 VDC) 

10 VDC maximum input voltage
Internal 75k ohm pull down

See guideline A in Table 5.

Analog input - Current Mode (4 VDC–20 mA) 

Internal 100 ohm load impedance

See guideline B

 

in Table 5.

Analog input - Resistive Mode (0 ohm–600k ohm)

Internal 11 V, 15k ohm pull up
Qualified sensors: 0k

2k ohm potentiometer, RTD (1k 

Nickel [Johnson Controls sensor], 1k Platinum, and A99B 

Silicon Temperature Sensor) NTC sensor (10k Type L, 10k 

Johnson Controls Type II, 2.252k Type II)

See guideline A in Table 5

.

Binary input - Dry Contact Maintained mode

 

1 second minimum pulse width
Internal 11 V, 15k ohm pull up

See guideline A in Table 5.

ICOM

n

Universal input common

 for all universal input terminals 

Note:

 All universal ICOM

n

 terminals share a common, 

which is not isolated from all other commons.

Same as (universal) IN

n

Содержание PEAK IOM57

Страница 1: ...the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver to secure wires in the te...

Страница 2: ...her devices or wiring can interfere with controller communication Observe these additional guidelines when you mount a field controller in a panel or enclosure Mount the controller so that the enclosu...

Страница 3: ...ole locations on the wall or surface Alternatively hold the controller up to the wall or surface in the proper mounting position and mark the hole locations through the mounting clips 3 Drill holes in...

Страница 4: ...IOM5711 physical features Callout Physical feature Description and references 1 Device address DIP Switch Block 2 Mounting clip 3 24 VAC Class 2 supply power terminal block 4 Cover lift tab 5 SA bus...

Страница 5: ...imentation avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des compo...

Страница 6: ...The SA bus supervisor advanced application field equipment controller FAC field equipment controller FEC or VAV modular assembly VMA supplies 15 VDC to devices on the SA bus that require power SA FC b...

Страница 7: ...instructions and project installation drawings for wiring details IMPORTANT Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across th...

Страница 8: ...set to the correct device address See Setting the device addresses 3 Set DIP switch 128 to ON enables wireless operation on the controller For more information about installing a controller in a wire...

Страница 9: ...powered UI Current input external source isolated UI Current input internal source 2 wire UI Current input internal source 3 wire UI Current input external source in loop UI Table 3 Termination detai...

Страница 10: ...nstructions 10 Feedback from EPP 1000 UI Dry contact UI Dry contact UO Voltage analog output AO 0 10 VDC output to actuator internal source UO Table 3 Termination details Part 3 of 3 Type of field dev...

Страница 11: ...irements and cables Part 1 of 2 Terminal block label Terminal label Function ratings requirements Determine wire size and maximum cable length UNIVERSAL inputs IOM5711 15 V 15 VDC power source for act...

Страница 12: ...owing maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum wire size or One wire per terminal 2 5 mm2 12 AWG maximum Note You must determine the required wire size for the high voltage 30...

Страница 13: ...maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297...

Страница 14: ...rminal blocks functions ratings requirements and cables Terminal block port label Terminal labels Function electrical ratings and requirements Recommended cable type1 1 See Table 5 to determine wire s...

Страница 15: ...FR1800 Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure that switch 128 is set to OFF Note Do not connect a controller with switch 128 set to ON to an active...

Страница 16: ...ch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note PEA...

Страница 17: ...be set as a terminating device on the bus Note The EOL termination rules for SA buses and FC buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed info...

Страница 18: ...D states LED label LED color Normal LED state Description of LED state POWER Green On steady Off steady No supply power or the controller s polyswitch resettable fuse is open Check output wiring for s...

Страница 19: ...ry outputs BOs or configurable outputs COs Ambient conditions Operating 40 C to 70 C 40 F to 158 F 10 to 90 RH noncondensing Storage 40 C to 80 C 40 F to 176 F 5 to 95 RH noncondensing Addressing DIP...

Страница 20: ...A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that these products are in compliance with the essen...

Страница 21: ...Modules Installation Instructions 21 PEAK and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Build...

Отзывы: