PEAK® IOM57 Input/Output Modules Installation Instructions

13

Cable and wire length guidelines

Table 5 defines cable length guidelines for the various wire sizes that you can use to wire low-voltage (<30 V) input 
and outputs. 

Maximum cable length versus load current

Use Figure 8

 

to estimate the maximum cable length relative to the wire size and the load current in mA when you 

wire the inputs and outputs.

Note:

Figure 8 applies to the low-voltage (<30 V) inputs and outputs only. The load that is connected to the relay 

and local electrical codes determines the required size and length for high-voltage (>30 V) relay outputs.

Table 5:  Cable length guidelines and recommended wire sizes for low-voltage (<30 V) inputs and outputs

Guideline

1

1.

The required wire sizes and lengths for high-voltage (>30V) relay outputs are determined by the load connected to the relay 

and local, national, or regional electrical codes. 

Wire size or gauge and type

Maximum cable length 
and type

Assumptions

A

1.5 mm

2

 (18 AWG) stranded copper

457 m (1,500 ft) twisted 

wire

100 mV maximum voltage drop
Depending on cable and the connected 

input or output device, you may have to 

define an offset in the setup software 

for the input or output point.

0.8 mm (20 AWG) stranded copper

297 m (975 ft) twisted wire

0.6 mm (22 AWG) stranded copper

183 m (600 ft) twisted wire

N/A (24 AWG) stranded copper

107 m (350 ft) twisted wire

B

1.5 mm

2

 (18 AWG) stranded copper

229 m (750 ft) twisted wire

100 mV maximum voltage drop
Depending on cable and the connected 

input or output device, you may have to 

define an offset in the setup software 

for the input or output point.

0.8 mm (20 AWG) stranded copper

137 m (450 ft) twisted wire

0.6 mm (22 AWG) stranded copper

91 m (300 ft) twisted wire

N/A (24 AWG) stranded copper

61 m (200 ft) twisted wire

C

See Figure 8 to select wire size or 

gauge. Use stranded copper wire.

See Figure 8 to determine 

cable length. Use twisted 

wire cable.

N/A

Figure 8:  Maximum wire length for low-voltage (<30 V) inputs and outputs by current and wire size

450

500

400

350

300

250

200

150

100

50

0

0 m (0 ft)

15.2 m (50 ft)

30.5 m (100 ft)

45.7 m (150 ft)

61 m (200 ft)

76.2 m (250 ft)

91.4 m (300 ft)

106.7 m (350 ft)

121.9 m (400 ft)

137.2 m (450 ft)

Load Current (mA)

Length

FI

G:

fe

c_

wi

re

_s

iz

e_

le

ng

th

1.5 mm  (18 AWG)

0.8 mm (20 AWG)

0.6 mm (22 AWG)

 

N/A (24 AWG )

Содержание PEAK IOM57

Страница 1: ...the mounting surface M4 screws or 8 screws One 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only Small straight blade screwdriver to secure wires in the te...

Страница 2: ...her devices or wiring can interfere with controller communication Observe these additional guidelines when you mount a field controller in a panel or enclosure Mount the controller so that the enclosu...

Страница 3: ...ole locations on the wall or surface Alternatively hold the controller up to the wall or surface in the proper mounting position and mark the hole locations through the mounting clips 3 Drill holes in...

Страница 4: ...IOM5711 physical features Callout Physical feature Description and references 1 Device address DIP Switch Block 2 Mounting clip 3 24 VAC Class 2 supply power terminal block 4 Cover lift tab 5 SA bus...

Страница 5: ...imentation avant de r aliser un branchement lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des compo...

Страница 6: ...The SA bus supervisor advanced application field equipment controller FAC field equipment controller FEC or VAV modular assembly VMA supplies 15 VDC to devices on the SA bus that require power SA FC b...

Страница 7: ...instructions and project installation drawings for wiring details IMPORTANT Connect 24 VAC supply power to the controller and all other network devices so that transformer phasing is uniform across th...

Страница 8: ...set to the correct device address See Setting the device addresses 3 Set DIP switch 128 to ON enables wireless operation on the controller For more information about installing a controller in a wire...

Страница 9: ...powered UI Current input external source isolated UI Current input internal source 2 wire UI Current input internal source 3 wire UI Current input external source in loop UI Table 3 Termination detai...

Страница 10: ...nstructions 10 Feedback from EPP 1000 UI Dry contact UI Dry contact UO Voltage analog output AO 0 10 VDC output to actuator internal source UO Table 3 Termination details Part 3 of 3 Type of field dev...

Страница 11: ...irements and cables Part 1 of 2 Terminal block label Terminal label Function ratings requirements Determine wire size and maximum cable length UNIVERSAL inputs IOM5711 15 V 15 VDC power source for act...

Страница 12: ...owing maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum wire size or One wire per terminal 2 5 mm2 12 AWG maximum Note You must determine the required wire size for the high voltage 30...

Страница 13: ...maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point 0 8 mm 20 AWG stranded copper 297...

Страница 14: ...rminal blocks functions ratings requirements and cables Terminal block port label Terminal labels Function electrical ratings and requirements Recommended cable type1 1 See Table 5 to determine wire s...

Страница 15: ...FR1800 Series Wireless Field Bus application For all hard wired SA and FC bus applications ensure that switch 128 is set to OFF Note Do not connect a controller with switch 128 set to ON to an active...

Страница 16: ...ch 128 Off Used for MS TP master devices controllers that are hardwired to an SA bus or FC bus 0 to 3 Switch 128 ON Reserved addresses for wired subordinate devices not for use on controllers Note PEA...

Страница 17: ...be set as a terminating device on the bus Note The EOL termination rules for SA buses and FC buses are different Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed info...

Страница 18: ...D states LED label LED color Normal LED state Description of LED state POWER Green On steady Off steady No supply power or the controller s polyswitch resettable fuse is open Check output wiring for s...

Страница 19: ...ry outputs BOs or configurable outputs COs Ambient conditions Operating 40 C to 70 C 40 F to 158 F 10 to 90 RH noncondensing Storage 40 C to 80 C 40 F to 176 F 5 to 95 RH noncondensing Addressing DIP...

Страница 20: ...A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls declares that these products are in compliance with the essen...

Страница 21: ...Modules Installation Instructions 21 PEAK and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2018 Johnson Controls Build...

Отзывы: