68
Table 19. Environmental and Safety (All Models)
208/230/240 V ac Models
Surge
Suppression
EN 61000-2-2
EN 61000-4-2, Level 4
EN 61000-4-3, Level 3
EN 61000-4-4, Level 4 (also on signal ports)
EN 6100-4-5, Level 4 Criteria A
EMC
Certifications
CE per IEC/EN 62040-2,
Class B
Class B
EMC
(Emissions)
IEC 62040-2:ed2:2005 / EN 62040-2:2006
Safety
Conformance
IEC 62040-1-1, IEC 60950-1
Agency
Markings
CE, CB
Operating
Temperature
0°C to 40°C (32°F to 104°F) in Online mode, with linear
derating for altitude
NOTE Thermal protection switches load to Bypass in case
of overheating.
Storage
-20°C to 40°C (-4°F to 104°F) with batteries