43
EPO
Input
Polarity setting
(6)
① Enter the setting interface. Press
and hold the function setting key
for more than 2 seconds, then
come to setting interface, Press and
hold the scroll key
for more than
half a second(less than 2 seconds),
select the function setting, choose
EPO Input polarity setting interface,
the letters “EPO” will flash.
② Enter the EPO Input Polarity
setting interface. Press and hold the
function setting key
for more
than half a second(less than 2
seconds), the letters “EPO” will
stop flashing. The letters below the
“EPO” will flash. Press and hold
the scroll key
for more than half
a second (less than 2 seconds),
select the EPO input polarity,
“+P”(open circuit execute EPO
function) or “–P”(short circuit
execute EPO function)
③ Confirm the setting. After
selecting EPO input polarity, press
and hold the function setting key
for more than half a second (less
than 2 seconds). Now, the setting is
confirmed.
④ Exit from the setting interface.
Press and hold function setting key
for more than half a second (less
than 2 seconds), exit from the
setting interface and return to main
interface.