24
Connecting the EBP(s)
To install the optional EBP(s) for a UPS:
1.
On the rear of the UPS, remove the cable retention clip covering
the battery connector. Retain the clip. See Figure 17.
2.
Installations with one EBP only. Remove the cable retention clip
covering the right or upper battery connector. Retain the clips.
3.
Installations with more than one EBP. For all EBPs except the last
EBP, remove the cable retention clips covering both battery
connectors. Do not remove the clip from the second battery
connector on the last EBP. Retain the clips.
CAUTION
A small amount of arcing may occur when connecting an EBP
to the UPS. This is normal and will not harm personnel. Insert
the EBP cable into the UPS battery connector quickly and
firmly.
4.
Plug the EBP cable(s) into the battery connector(s) as shown in
Figure 17. Up to four EBPs may be connected to the UPS.
5.
Verify that the EBP connections are tight and that adequate
bend radius and strain relief exist for each cable.
6.
Continue to “UPS Initial Startup” on page 26.
Remove cable retention clip. Plug in EBP cable. Retain the clip