66
3K
IEC320 C20-16A
IEC320 C19-16A
Table 17. Electrical Output (All Models)
High Voltage Models
Nominal Outputs
200/208/220/230/240V
(voltage configurable or
auto-sensing)
1000/2000/3000 VA
0.9/1.8/2.7 kW
Frequency
50 or 60 Hz, autosensing
Output Overload
(Normal Mode)
108%±5%–150%±5%: Load transfers to Fault mode
after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode
after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Output Overload
(Bypass Mode)
100%±5%–130%±5%: Load transfers to Fault mode
after 20 minutes.
130%±5%–150%±5%: Load transfers to Fault mode
after 2 minutes.
150%±5%–200%±5%: Load transfers to Fault mode
after 15 seconds.
>200%±5%: Load transfers to Fault mode after 140
ms.
Output Overload
(Battery Mode)
108%±5%–150%±5%: Load transfers to Fault mode
after 30 seconds.
150%±5%–200%±5%: Load transfers to Fault mode
after 300 ms.