D-121
Parameter Reference
AC30V series Variable Speed Drive
Trips Status
Parameters::Trips::Trips Status
PNO Parameter Descriptions
First Trip
An enumerated value that shows the trip that caused the AC30 to disable the stack. When multiple trips are active at the same time,
(for example Over Current followed by Over Temperature), this parameters shows the first trip that the AC30 detected. Refer to
Chapter 10 “Trips and Fault Finding”, for details of each trip source.
Enable 1 - 32
A 32-bit word that can be used to enable, (or disable), individual trips. Refer to Chapter 10 “Trips and Fault Finding” for details of the
value corresponding to each trip.
Active 1 - 32
A 32-bit word that indicates which trip sources are active. For example, the HEATSINK OVERTEMP may remain true for some time
after the initial fault is reported.
The Active value shows active trip sources even if the corresponding trip is not enabled in “Enabled 1-32”.
Refer to Chapter 10 “Trips and Fault Finding” for details of the value corresponding to each trip.
Warnings 1 - 32
A 32-bit word that indicates trip sources that are close to a fault condition. For example, the heat sink fault monitoring firmware
reports a HEATSINK OVERTEMP warning when the heat sink temperature gets close to the heat sink fault level.
The Warnings value is not affected by the trip enable mask, “Enabled 1-32”.
Refer to Chapter 10 “Trips and Fault Finding” for details of the value corresponding to each trip.
Содержание AC30V Series
Страница 140: ...9 24 Setup Wizard AC30V series Variable Speed Drive MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 141: ...Setup Wizard 9 25 AC30V series Variable Speed Drive Figure 9 16 Charting Drive Parameters...
Страница 205: ...Compliance C 10 AC30V series Variable Speed Drive Frame H Frame J Frame K contact Parker for more information...
Страница 341: ...Parameter Reference D 102 AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...