C-33
Compliance
AC30V series Variable Speed Drive
Supply Harmonic Analysis (Frame J - Normal Duty)
Assumptions: Rsce ≥ 120 at 400V where Q
1n
is the rated rms value of the fundamental voltage of the supply
transformer. The results conform to IEC61000-3-12:2011.
Fundamental Voltage (V)
400
Drive Type
Three Phase
Motor Power
(kW)
90
110
132
90
110
132
Typical Motor
Efficiency %
92
92
92
92
92
92
Harmonic No.
RMS Current (A)
Harmonic No.
RMS Current (A)
1
145
180.9
217.0
25
3.7
3.9
4.4
3
0.0
0.0
0.0
27
0.0
0.0
0.0
5
51.0
59.5
70.4
29
3.5
3.4
3.8
7
27.1
26.4
29.7
31
2.8
2.8
3.1
9
0.0
0.0
0.0
33
0.0
0.0
0.0
11
12.2
14.8
17.5
35
2.6
2.4
2.5
13
8.4
8.9
10.2
37
2.2
2.1
2.2
15
0.0
0.0
0.0
39
0.0
0.0
0.0
17
7.0
8.0
9.3
40
0.0
0.0
0.0
19
5.1
5.5
6.4
Total RMS
Current (A)
157.5
193.4
231.4
21
0.0
0.0
0.0
23
4.8
5.1
5.8
* THD
(I
) %
41.9
37.89
37.06
* (Total Harmonic Distortion)
THD(V) x 100
Q
Q
h2
1n
h 40
h 2
%
Содержание AC30V Series
Страница 140: ...9 24 Setup Wizard AC30V series Variable Speed Drive MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 141: ...Setup Wizard 9 25 AC30V series Variable Speed Drive Figure 9 16 Charting Drive Parameters...
Страница 205: ...Compliance C 10 AC30V series Variable Speed Drive Frame H Frame J Frame K contact Parker for more information...
Страница 341: ...Parameter Reference D 102 AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...