10-3
Trips & Fault Finding
AC30V series Variable Speed Drive
ID
Trip Name
Possible Reason for Trip
8
INVERSE TIME
A prolonged overload condition, exceeding the Inverse Time allowance, has caused the trip:
Remove the overload condition
9
MOTOR I2T
Only for PMAC Motor: A prolonged load condition, exceeding the motor rated current, has caused the trip. The
estimated motor load has reached a value of 105%
10
LOW SPEED I
The motor is drawing too much current (>100%) at zero output frequency:
FIXED BOOST level set too high
11
HEATSINK OVERTEMP
Drive heatsink temperature too high
The ambient air temperature is too high
Poor ventilation or spacing between drives
Check heatsink fan is rotating
12
INTERNAL OVERTEMP
Processor temperature or ambient temperature within the power stage too high
The ambient temperature in the drive is too high
13
MOTOR OVERTEMP
The motor temperature is too high, (required IO Option card)
Excessive load
Motor voltage rating incorrect
FIXED BOOST level set too high
Prolonged operation of the motor at low speed without forced cooling
Break in motor thermistor connection
14
EXTERNAL TRIP
The external (application) trip input is high:
Refer to the application description to identify the source of the signal
15
BRAKE SHORT CCT
External dynamic brake resistor has been overloaded:
The external dynamic brake has developed a short circuit.
Wiring fault
16
BRAKE RESISTOR
External dynamic brake resistor has been overloaded:
Trying to decelerate a large inertia too quickly or too often
17
BRAKE SWITCH
Internal dynamic braking switch has been overloaded:
Trying to decelerate a large inertia too quickly or too often
18
LOCAL CONTROL
Keypad has been disconnected from drive whilst drive is running in Local Control:
GKP accidentally disconnected from drive
Содержание AC30V Series
Страница 140: ...9 24 Setup Wizard AC30V series Variable Speed Drive MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 141: ...Setup Wizard 9 25 AC30V series Variable Speed Drive Figure 9 16 Charting Drive Parameters...
Страница 205: ...Compliance C 10 AC30V series Variable Speed Drive Frame H Frame J Frame K contact Parker for more information...
Страница 341: ...Parameter Reference D 102 AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...