Parameter Reference
D-26
AC30V series Variable Speed Drive
Functional Description
During a fast deceleration, the kinetic energy of the motor load is regenerated to the drive, charging the DC link capacitors.
When the
VDC Lim Level
is reached, the speed septoint is held, waiting for the DC link to go below
VDC Lim Level
.
When the DC link falls below this level, the speed setpoint is released and is ramped down using system ramp deceleration.
This sequence is run until the speed septoint reaches the user speed demand.
By Default,
VDC Lim Level
is set to the same value as the braking threshold.
This feature is run at a rate of 1 milli-second.
Ramp
Power Loss
Ride Thru
DC Link
Volts Limit
Slew Rate
(V/Hz only)
Speed Setpoint path
User
Speed control loop
Содержание AC30V Series
Страница 140: ...9 24 Setup Wizard AC30V series Variable Speed Drive MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 141: ...Setup Wizard 9 25 AC30V series Variable Speed Drive Figure 9 16 Charting Drive Parameters...
Страница 205: ...Compliance C 10 AC30V series Variable Speed Drive Frame H Frame J Frame K contact Parker for more information...