D-59
Parameter Reference
AC30V series Variable Speed Drive
Minimum Speed
Setup::Application::Minimum Speed
Function availability depends on macro selected.
The minimum speed function is used to determine how the AC30V will follow a reference. There are two modes:
Functional Description
There are two operating modes for the
MINIMUM SPEED
function:
PROP WITH MINIMUM (proportional with minimum)
In this mode the
MINIMUM SPEED
function behaves like a simple clamp. The
Minimum Speed
Value
has the valid range -100% to 100% and the output is always greater than or equal to the
Minimum Speed Value
.
LINEAR
In this mode the
MINIMUM SPEED
function first clamps the input to zero then rescales the input such
that the output goes linearly between minimum and 100% for an input that goes from 0 to 100%.
Note the constraints:-
min >= 0
input >= 0
max = 100%
PNO Parameter Descriptions
Minimum Speed Value
Specifies the minimum output value.
Minimum Speed Mode
There are two modes of operation:
Enumerated Value:
0 :
PROP WITH MINIMUM
1 :
LINEAR
Min
0
100%
100
-100
input
output
Содержание AC30V Series