6-29
Safe Torque Off
AC30V series Variable Speed Drive
THE FOLLOWING TEST STEPS MUST BE PERFORMED:
Initial Check
:
STO test
Comprehensive Check, Activity
Expected reaction and effect
1
Ensure that no harm can come to personnel or equipment if the motor turns.
2
Apply +24V DC to terminals X10/01 and X10/03.
3
Switch on power to the drive.
No error must be present in the drive system.
X10/05 and /06 must be OFF.
4
Configure the drive and associated equipment if necessary so that it can be started
and stopped, and a speed setpoint provided.
No error must be present in the drive system.
X10/05 and /06 must be OFF.
5
Try to start the drive with a non-zero setpoint. This setpoint value will be referred to as
SPT1 for brevity in these tests. Leave this set throughout all tests.
Drive must start and motor must turn at SPT1.
X10/05 and /06 must be OFF.
Содержание AC30V Series
Страница 140: ...9 24 Setup Wizard AC30V series Variable Speed Drive MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 141: ...Setup Wizard 9 25 AC30V series Variable Speed Drive Figure 9 16 Charting Drive Parameters...
Страница 205: ...Compliance C 10 AC30V series Variable Speed Drive Frame H Frame J Frame K contact Parker for more information...
Страница 341: ...Parameter Reference D 102 AC30V series Variable Speed Drive Setpoint Drive Frequency Frequency 1 Frequency 2...