Programming Your Application
6-10
650G AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SKIP FREQUENCY
2
This parameter contains the centre frequency of
skip band 2 in Hz
0.0 to 240.0 Hz
0.0
SKIP FREQUENCY
BAND 2
The width of skip band 2 in Hz
0.0 to 60.0 Hz
0.0
AUTO RESTART
ATTEMPTS
Determines the number of restarts that will be
permitted before requiring an external fault reset
0 to 10
0
AUTO RESTART
DELAY
Determines the delay between restart attempts for
a trip included in AUTO RESTART TRIGGERS and
AUTO RESTART T. The delay is
measured from all error conditions clearing
0.0 to 600.0 s
10.0
AUTO RESTART
TRIGGERS
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 7: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF
0x0000
AUTO RESTART
T
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 7: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF
0x0000
DB ENABLE
Enables operation of the dynamic braking.
0=FALSE
1=TRUE
1
DB RESISTANCE
The value of the load resistance.
1 to 1000
product
code
dependent
DB POWER
The power that the load resistance may continually
dissipate.
0.1 to 510.0 kW
product
code
dependent
DB OVER-RATING Multiplier that may be applied to DB POWER for
power overloads lasting no more than 1 second.
1 to 40
25
TORQUE
FEEDBACK
Shows the estimated motor torque, as a
percentage of rated motor torque.
—
.xx %
—
.xx %
TORQUE LEVEL
This parameter sets the value of load at which AT
LOAD becomes TRUE. AT LOAD may be
connected to a digital output. Refer to
s
DOP1 to
s
DOP3. 100% = rated torque for the motor.
-300.0 to 300.0 %
100.0 %
USE ABS
TORQUE
F
When TRUE, the direction of rotation is ignored. In
this case, the comparison level should always be
positive.
When FALSE, the direction of rotation is not
ignored. Driving a load in the reverse direction
gives a negative value for torque. In this case, the
comparison level may be positive or negative.
0=FALSE
1=TRUE
0
LOCAL MIN
SPEED
F
The magnitude of the minimum setpoint that will
be used when running in Local Mode.
0.0 to 100.0 %
0.0 %
www.comoso.com
Содержание 650G series
Страница 2: ...www comoso com ...
Страница 30: ...3 9 Installing the Drive 650G AC Drive Through Panel Cutout Details www comoso com ...
Страница 32: ...3 11 Installing the Drive 650G AC Drive Duct Kit Installation Diagram www comoso com ...
Страница 49: ...Installing the Drive 3 28 650G AC Drive Figure 3 14 Footprint Bookcase Mounting Filters generic www comoso com ...
Страница 153: ...Applications 13 12 650G AC Drive www comoso com ...