6-9
Programming Your Application
650G AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::SERL Menu
REMOTE COMMS
SEL
F
Selects the type of remote communications mode:
0 : FALSE, and in REMOTE mode then control is
from the terminals.
1 : TRUE, and in REMOTE mode then control is
from the communications.
0=FALSE
1=TRUE
0
COMMS
TIMEOUT
F
Se
ts the maximum time allowed between
refreshing the COMMS COMMAND parameter.
The drive will trip if this time is exceeded. Set the
time to 0.00 seconds to disable this feature.
0.0 to 600.0s
0.0s
COMMS
ADDRESS
F
The drives identity address.
Note: if set to 0, it will only respond to broadcast
messages.
0 to 255
0
BAUD RATE
F
Selects the Baud Rate for the MODBUS protocol.
0 : 1200
1 : 2400
2 : 4800
3 : 7200
4 : 9600
5 : 14400
6 : 19200
7 : 38400
8 : 57600
4
PARITY
F
Selects the Parity for the MODBUS protocol.
0= NONE
1= ODD
2= EVEN
0
REPLY DELAY ms The time in milliseconds between the drive
receiving the complete request from the
communications master (PLC/PC) and replying to
this request.
0 to 200
5
OP PORT
PROTOCOL
F
Selects the protocol to be used by the keypad port
on the front of the drive. When EIBISYNC ASCII is
selected, BAUD RATE is 19200 and PARITY is
EVEN. FIELDBUS is reserved for future use.
0= AUTOMATIC
1= KEYPAD
2=EIBISYNC ASCII
3= MODBUS
4= FIELDBUS
0
P3 PORT
PROTOCOL
F
Selects the protocol to be used by the RS232
programming port on the drive's control board.
When EIBISYNC ASCII is selected, BAUD RATE is
19200 and PARITY is EVEN. FIELDBUS is reserved
for future use.
As
S
SE07 0
SET::SETP Menu
JOG ACCEL TIME As
P
4, for Jog
0.0 to 3000.0s
1.0
JOG DECEL TIME As
P
5, for Jog
0.0 to 3000.0s
1.0
RAMP TYPE
Selects the ramp type
0=LINEAR
1=S
0
S RAMP JERK
Rate of change of acceleration of the curve in units
per second³
0.01 to 100.00 s3
10.00
S RAMP
CONTINUOUS
When TRUE and the S ramp is selected, forces a
smooth transition if the speed setpoint is changed
when ramping. The curve is controlled by the S
RAMP JERK parameter. When FALSE, there is an
immediate transition from the old curve to the new
curve
0=FALSE
1=TRUE
1
MIN SPEED
MODE
Selects a mode to determine how the drive will
follow a reference: Proportional : minimum limit,
Linear : between minimum and maximum.
0=PROP.W/MIN.
1=LINEAR (used by
the 601 product)
0
SKIP FREQUENCY
1
This parameter contains the centre frequency of
skip band 1 in Hz
0.0 to 240.0 Hz
0.0
SKIP FREQUENCY
BAND 1
The width of skip band 1 in Hz
0.0 to 60.0 Hz
0.0
www.comoso.com
Содержание 650G series
Страница 2: ...www comoso com ...
Страница 30: ...3 9 Installing the Drive 650G AC Drive Through Panel Cutout Details www comoso com ...
Страница 32: ...3 11 Installing the Drive 650G AC Drive Duct Kit Installation Diagram www comoso com ...
Страница 49: ...Installing the Drive 3 28 650G AC Drive Figure 3 14 Footprint Bookcase Mounting Filters generic www comoso com ...
Страница 153: ...Applications 13 12 650G AC Drive www comoso com ...