Certification for the Drive
10-4
650G AC Drive
Single VSD - Multiple Motors
Note:
Refer to Chapter 11: “Applications” - Using Multiple Motors on a Single Drive.
If connecting multiple motors to a single VSD, use a star junction point for motor cable
connections. Use a metal box with entry and exit cable glands to maintain shield integrity.
Refer to Chapter 11: “Applications” - Using Multiple Motors on a Single Drive.
Star Point Earthing
A star-point earthing policy separates ‘noisy’ and ‘clean’ earths. Four separate earth busbars
(three are insulated from the mounting panel) connect to a single earth point (star point) near the
incoming safety earth from the main supply. Flexible, large cross-section cable is used to ensure
a low HF impedance. Busbars are arranged so that connection to the single earth point is as
short as possible.
1 Clean Earth Busbar (insulated from the mounting panel)
Used as a reference point for all signal and control cabling. This may be further subdivided into
an analog and a digital reference busbar, each separately connected to the star earthing point.
The digital reference is also used for any 24V control.
Note:
The 650G uses a single clean earth busbar for analog and digital.
2 Dirty Earth Busbar (insulated from the mounting panel)
Used for all power earths, i.e. protective earth connection. It is also used as a reference for any
110 or 220V control used, and for the control transformer screen.
3 Metal Work Earth Busbar
The back panel is used as this earth busbar, and should provide earthing points for all parts of
the cubicle including panels and doors. This busbar is also used for power screened cables
which terminate near to (10cm) or directly into a VSD - such as motor cables, braking choppers
and their resistors, or between VSDs - refer to the appropriate product manual to identify these.
Use U-clips to clamp the screened cables to the back panel to ensure optimum HF connection.
4 Signal/Control Screen Earth Busbar (insulated from the mounting panel)
Used for signal/control screened cables which
do not
go directly to the VSD. Place this busbar
as close as possible to the point of cable entry. ‘U’ clamp the screened cables to the busbars to
ensure an optimum HF connection.
www.comoso.com
Содержание 650G series
Страница 2: ...www comoso com ...
Страница 30: ...3 9 Installing the Drive 650G AC Drive Through Panel Cutout Details www comoso com ...
Страница 32: ...3 11 Installing the Drive 650G AC Drive Duct Kit Installation Diagram www comoso com ...
Страница 49: ...Installing the Drive 3 28 650G AC Drive Figure 3 14 Footprint Bookcase Mounting Filters generic www comoso com ...
Страница 153: ...Applications 13 12 650G AC Drive www comoso com ...