9-22
Technical Specifications
650G AC Drive
Supply Harmonic Analysis (Frame D Normal Duty)
Assumptions: 10000A short circuit supply capability
, equivalent
to 73
H supply impedance at 400V
where Q
1n
is the rated rms
value of the fundamental voltage of the supply transformer. The
results conform to stage 1, stage 2 and stage 3 of the
Engineering Recommendation G.5/3 September 1976,
Classification ‘C’: Limits for Harmonics in the UK Electricity
Industry.
THD(V) x 100
Q
Q
h2
1n
h 40
h 2
%
Fundamental
Voltage (V)
230 400
500
Inverter Type
Three Phase
Motor Power
(kW)
11.0 15.0 18.0 15.0 18.0 22.0 30.0 15.0 18.0 22.0 30.0
Typical
Motor
Efficiency %
90 90 90 90 90 90 90 90 90 90
Harmonic
No.
RMS Current (A)
1
47.2 59.2
30.6 36.3 48.2 67.7 23.4 29.0 38.6
*
3
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.1 0.0
5
22.5 23.3
21.6 24.8 31.0 41.7 17.6 20.9 26.6
7
12.5 11.5
14.7 16.4 19.6 25.5 13.0 14.7 17.8
9
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
11
3.3 4.4
3.7 3.6 3.4 4.0 4.5 4.2 4.1
13
2.7 3.0
2.0 2.4 3.3 4.7 2.1 2.1 2.6
15
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
17
1.8 2.5
1.7 1.8 1.8 2.1 1.6 1.8 2.0
19
1.3 1.7
1.1 1.1 1.4 1.9 1.3 1.3 1.2
21
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
23
1.2 1.6
0.9 1.0 1.0 1.3 0.6 0.8 1.1
25
0.9 1.2
0.7 0.8 0.8 1.1 0.6 0.8 0.8
27
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
29
0.8 1.1
0.5 0.6 0.6 0.9 0.4 0.4 0.6
31
0.7 0.9
0.5 0.5 0.6 0.7 0.4 0.4 0.5
33
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
35
0.6 0.8
0.3 0.3 0.4 0.6 0.3 0.3 0.4
37
0.5 0.7
0.3 0.3 0.5 0.5 0.3 0.3 0.4
39
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
40
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
41
0.4 0.6
0.2 0.2 0.2 0.5 0.2 0.2 0.3
42
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
43
0.4 0.5
0.2 0.2 0.4 0.4 0.2 0.2 0.2
44
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
45
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
46
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
47
0.3 0.4
0.2 0.2 0.2 0.3 0.1 0.2 0.2
48
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
49
0.3 0.4
0.2 0.2 0.3 0.3 0.1 0.2 0.2
50
0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0
Total RMS
Current (A)
54.0 65.0
40.5 47.2 60.8 83.8 32.6 39.1 50.5
THD (V) %
0.97 1.05 0.96 1.08 1.30 1.72 0.85 0.96 1.16
* Please contact Parker SSD Drives
www.comoso.com
Содержание 650G series
Страница 2: ...www comoso com ...
Страница 30: ...3 9 Installing the Drive 650G AC Drive Through Panel Cutout Details www comoso com ...
Страница 32: ...3 11 Installing the Drive 650G AC Drive Duct Kit Installation Diagram www comoso com ...
Страница 49: ...Installing the Drive 3 28 650G AC Drive Figure 3 14 Footprint Bookcase Mounting Filters generic www comoso com ...
Страница 153: ...Applications 13 12 650G AC Drive www comoso com ...