Installing the Drive
3-14
650G AC Drive
Control Terminal Description Frames C, D, E & F
Terminal
(SELV)
Description
Application 1 Default Function
(for other Applications refer to Chapter 13: “Applications”)
Range
Scn
RS485 option Scn=Screen (shield)
-
B RS485
option
B=RxB/TxB
-
A RS485
option
A=RxA/TxA
-
P3
P3
RS232 port for use with remote-mounted 6521 and 6901
Keypad or programming PC
-
RL1A User
Relay
Volt-free normally-open relay contact
Default function DOUT3 closed = HEALTH
0-250Vac/24Vdc 6A
RL1B User
Relay
Volt-free normally-open relay contact
Default function DOUT3 closed = HEALTH
0-250Vac/24Vdc 6A
13
DIN7 (ENC B) Configurable digital input
0-24V
12
DIN6 (ENC A) Configurable digital input
0-24V
11 DIN5
Not Coast Stop - configurable digital input:
0V = drive may run, 24V = Coast to Stop
0-24V
10 DIN4/
DOUT2
Configurable digital input/output
Not Stop (input):
24V = RUN FWD & RUN REV signals latched
0V = RUN FWD & RUN REV signals not latched
0-24V source open
collector *
9 DIN3/
DOUT1
Configurable digital input/output
Jog (input):
0V = Stop, 24V = Jog
0-24V
8 DIN2
Direction – configurable digital input:
0V = Remote Forward, 24V = Remote Reverse
0-24V
7 DIN1
Run Forward – configurable digital input: 0V = Stop, 24V =
Run
0-24V
6
+24V
24V supply for digital I/O
*
5
AOUT1
Ramp Output – configurable analog output (10mA maximum
loading)
0-10V
4
10VREF
10V reference (10mA maximum loading)
10V
3
AIN2
Speed Trim – analog input 2
0-10V, 0-5V
0-20mA, 4-20mA
2
AIN1
Speed Setpoint – analog input 1. If unused, tie this input to
0V.
0-10V, 0-5V
1
0V
0V reference for analog/digital I/O
0V
*
The total current available is 150mA, either individually or as the sum of terminal 6 & 10.
Motor Thermistor Connections
This input is provided to detect over-temperature in motors fitted with an internal thermistor.
There is no polarity to the thermistor connections.
IMPORTANT:
This input provides “Basic” insulation only to the SELV control circuits and assumes the
motor has “Basic” insulation to the windings/mains circuits.
The thermistor type supported is PTC `Type A’ as defined in IEC 34-11 Part 2. The drive uses
the following resistance thresholds:
Rising temperature trip resistance:
1650 to 4000
Falling temperature trip reset resistance:
750 to 1650
If the motor is not fitted with an internal
thermistor, you should disable the thermistor
trip function either by setting INVERT
THERMISTOR INPUT (
S
Ot) to 1, or by
linking the thermistor terminals.
TRIPS MENU
www.comoso.com
Содержание 650G series
Страница 2: ...www comoso com ...
Страница 30: ...3 9 Installing the Drive 650G AC Drive Through Panel Cutout Details www comoso com ...
Страница 32: ...3 11 Installing the Drive 650G AC Drive Duct Kit Installation Diagram www comoso com ...
Страница 49: ...Installing the Drive 3 28 650G AC Drive Figure 3 14 Footprint Bookcase Mounting Filters generic www comoso com ...
Страница 153: ...Applications 13 12 650G AC Drive www comoso com ...