9-12
Technical Specifications
650G AC Drive
Cabling Requirements for EMC Compliance (Frame 1, 2 & 3)
Power Supply Cable Motor Cable
Brake Resistor Cable Signal/Control Cable
Cable Type
(for EMC Compliance)
Unscreened Screened/armoured
Screened/armoured Screened
Segregation
From all other
wiring (clean)
From all other wiring (noisy)
From all other wiring
(sensitive)
Length Limitations
With Internal AC Supply
EMC Filter
Unlimited *25
metres
25 metres
25 metres
Length Limitations
Without Internal AC
Supply EMC Filter
Unlimited
25 metres
25 metres
25 metres
Screen to Earth
Connection
Both ends
Both ends
Drive end only
Output Choke
300 metres maximum
* Maximum motor cable length under any circumstances
EMC Compliance Frames C, D, E & F
Standard EN 61800-3
Frame C
Frame D
Frame E
Frame F
Conducted
emissions
Table 14
Unrestricted
Distribution
Category C1
When fitted with the
specified external
filter
When fitted with the
specified external
filter
When fitted with the
specified external
filter
When fitted with the
specified external
filter
Conducted
emissions
Table 14
Category C2
Restricted
Distribution
When fitted with the
specified external
filter
When fitted with the
specified external
filter
When fitted with the
specified external
filter
When fitted with the
specified external
filter
Radiated
Emissions
Table 15
Category C1
Unrestricted
Distribution
No No No No
Radiated
Emissions
Table 15
Category C2
Restricted
Distribution
Yes Yes Yes Yes
Conducted
emissions
Table 17
Category C3
Where
I<=100A
Yes Yes Yes Yes
Conducted
emissions
Table 17
Category C3
Where I>=100A
N/A
N/A
N/A
Yes
Radiated
Emissions
Table 18
Category C3
Second
environment
Yes Yes Yes Yes
Cabling Requirements for EMC Compliance (Frames C, D, E & F)
Power Supply
Cable
Motor Cable External AC Supply EMC
Filter to Drive Cable
Brake Resistor
Cable
Signal/Control
Cable
Cable Type
(for EMC Compliance)
Unscreened Screened/
armoured
Screened/
armoured
Screened/
armoured
Screened
Segregation
From all
other wiring
(clean)
From all other wiring (noisy)
From all other
wiring (sensitive)
Length Limitations
With External AC Supply
EMC Filter
Unlimited
50 metres
0.3 metres
25 metres
25 metres
Screen to Earth
Connection
Both ends
Both ends
Both ends
Drive end only
Output Choke
300
metres
maximum
* Maximum motor cable length under any circumstances
www.comoso.com
Содержание 650G series
Страница 2: ...www comoso com ...
Страница 30: ...3 9 Installing the Drive 650G AC Drive Through Panel Cutout Details www comoso com ...
Страница 32: ...3 11 Installing the Drive 650G AC Drive Duct Kit Installation Diagram www comoso com ...
Страница 49: ...Installing the Drive 3 28 650G AC Drive Figure 3 14 Footprint Bookcase Mounting Filters generic www comoso com ...
Страница 153: ...Applications 13 12 650G AC Drive www comoso com ...