3-7
Installing the Drive
650G AC Drive
Minimum Air Clearance (Frame E)
Cubicle-Mount Product/Application (Frame E)
(Europe: IP2x, USA/Canada: Open Type).
The drive, without the top cover fitted, must be mounted in a suitable cubicle.
J
K
L
ISOLATED FORCED AIR FLOWS
M
Figure 8 Air Clearance for a Cubicle-Mount Product/Application
Model Recognition
Clearances for Standard Product without Top Cover (mm)
J
K
L
M
Frame E
0 (zero)
25
70
70
Wall-Mount Product/Application (Frame E)
(Europe: IP2x plus IP4x top surface protection, USA/Canada: Type 1).
Wall-mounted 650G units
must
have the top cover correctly fitted. The top cover fixing screw
has a maximum tightening torque of 1.5Nm (1.2Nm recommended).
J
K
L
M
ISOLATED FORCED AIR FLOWS
Top Cover
Figure 9 Air Clearance for a Wall-Mount Product/Application
Model Recognition
Clearances for Standard Product fitted with Top Cover (mm)
J
K
L
M
Frame E
0 (zero)
25
70
70