ACCULINK 3172 and 3174 E1 DSU/CSU
2-6
March 1999
3170-A2-GB20-30
Installing the Single –
48 Vdc Power Supply
To install the E1 DSU/CSU using a single source
– 48 Vdc power supply, refer to Figure 2-11 and use the
following procedure.
To install the – 48 Vdc single source power supply:
"
Procedure
1. Connect the black and red wires to the – 48 Vdc
return source.
2. Connect the green wire to a suitable ground.
3. Connect the orange and blue wires to the –
48 Vdc
input source.
4. Cut the white wire off at the outer insulation.
5. Plug the power connector into the E1 DSU/CSU.
1
2
3
4
5
6
BLACK
RED
GREEN
WHITE
ORANGE
BLUE
– 48 VDC INPUT
99-14299-02
X
GROUND
DSU/CSU POWER
PLUG
TO CUSTOMER-SUPPLIED BATTERY
– 48 VDC RETURN
Figure 2-11. –
48 Vdc Single Source Power Supply Pinouts
Содержание 3172
Страница 1: ...ACCULINK 3172 AND 3174 E1 DSU CSU OPERATOR S GUIDE Document No 3170 A2 GB20 30 March 1999 ...
Страница 6: ...ACCULINK 3172 and 3174 E1 DSU CSU E March 1999 3170 A2 GB20 30 ...
Страница 16: ...ACCULINK 3172 and 3174 E1 DSU CSU 1 6 March 1999 3170 A2 GB20 30 This page intentionally left blank ...
Страница 26: ...ACCULINK 3172 and 3174 E1 DSU CSU 2 10 March 1999 3170 A2 GB20 30 This page intentionally left blank ...
Страница 64: ...ACCULINK 3172 and 3174 E1 DSU CSU 3 38 March 1999 3170 A2 GB20 30 This page intentionally left blank ...
Страница 90: ...ACCULINK 3172 and 3174 E1 DSU CSU 4 26 March 1999 3170 A2 GB20 30 This page intentionally left blank ...
Страница 92: ...ACCULINK 3172 and 3174 E1 DSU CSU A 2 March 1999 3170 A2 GB20 30 This page intentionally left blank ...
Страница 138: ...ACCULINK 3172 and 3174 E1 DSU CSU D 16 March 1999 3170 A2 GB20 30 This page intentionally left blank ...
Страница 162: ...ACCULINK 3172 and 3174 E1 DSU CSU H 2 March 1999 3170 A2 GB20 30 This page intentionally left blank ...
Страница 172: ...ACCULINK 3172 and 3174 E1 DSU CSU Glossary 10 March 1999 3170 A2 GB20 30 This page intentionally left blank ...