34
Magellan & Spectra SP • Installation Guide
Force Zones
Sections
[001]
to
[032]
: Zones 1 to 32
Option
[8]
OFF= Force Zone Disabled
Option
[8]
ON= Selected Zone is Force Enabled (default)
Any open Force Zones at the time of arming will be considered deactivated by the control panel. If during this period a deactivated zone is closed, the control panel
will revert that zone to active status. Consequently, the control panel will generate an alarm if the zone is breached.
Do not program a fire zone with the Force option, as the control panel will never bypass fire zones when Force arming.
EOL Zones
Section
[706]
: Zone Options
Option
[2]
OFF= Zones do not use EOL resistors (default)
Option
[2]
ON= Zones require EOL resistors
If all detection devices connected to the control panel have input terminals that require 1K
end of line resistors, enable option
[2]
in section
[706]
. For details on
using EOL resistors, See “Single Zone Inputs” on page 18
ATZ Zone Doubling
Section
[705]
: General Zone Options
Option
[1]
OFF= ATZ zone doubling disabled (default)
Option
[1]
ON= ATZ zone doubling enabled
Enabling ATZ Zone Doubling allows you to install two detection devices per input terminal.
Tamper Input on ZX8/ZX82 ID A (Panel + 1)
Section
[706]
: General Zone Options 2
Option
[4]
OFF= Zone A (default)
Option
[4]
ON= Tamper input
Enabling this option will make the first zone on the ZX8/ZX82 ID A (Panel +1) a tamper input. By default, it is a zone.
Tamper Input on ZX8/ZX82 ID B (Panel + 9)
Section
[706]
: General Zone Options 2
Option
[5]
OFF= Zone B (default)
Option
[5]
ON= Tamper input
Enabling this option will make the first zone on the ZX8/ZX82 ID B (Panel +9) a tamper input. By default, it is a zone.
Tamper Input on ZX8/ZX82 ID C (Panel + 17)
Section
[706]
: General Zone Options 2
Option
[6]
OFF= Zone C (default)
Option
[6]
ON= Tamper input
Enabling this option will make the first zone on the ZX8/ZX82 ID C (Panel +17) a tamper input. By default, it is a zone.
ATZ Wiring Options
Section
[705]
: General Zone Options
Option
[2]
OFF= ATZ Series (default)
Option
[2]
ON= ATZ Parallel doubling enabled
ATZ Zone Doubling can be configured in either a series or parallel connection.
Zone Input 1 Becomes a 2-wire Smoke Input
Section
[706]
: General Zone Options
Option
[3]
OFF= Zone input 1 is a standard zone input (default)
Option
[3]
ON= Zone input 1 becomes a 2-wire smoke input
With this option enabled, zone input 1 becomes a 2-wire smoke input (all panels except SP5500).
Zone Timers
Sections
[041]
to
[044]
: Zones 1 to 4
001 to 255 x 10 ms, Default = 060
The Zone Timer defines how quickly the control panel will respond to an open zone. The control panel will not display an open zone on the keypad or generate an
alarm until the programmed Zone Timer has elapsed. All other zone definitions and options do not come into effect until the Zone Timer has elapsed. This feature
prevents any momentary glitches from causing an alarm or unnecessary reporting.