background image

Magellan & Spectra SP • Installation Guide

7

Installation

Location and Mounting

Before mounting the metal box, push the five white nylon mounting studs into the back of the box. Pull all cables into the cabinet and prepare them for connection 
before mounting the circuit board into the back of the cabinet. For the MG5075, if tamper is required, remove the PCB from the plastic enclosure prior to mounting. 
Select a centralized installation site on the main floor that isn't easily accessible to intruders and leave at least 5cm (2in) around the panel box to permit adequate 
ventilation and heat dissipation. The installation site should be dry and close to an AC source, ground connection and telephone line connection. Avoid installation 
near or in the path of strong RF fields (i.e. neon lights, computers), on or near metal objects, circuit breaker boxes, air conditioners and heater ducts since they may 
cause interference and reduce sensitivity. Avoid installing the control panel in the basement.

 IMPORTANT: To comply to EN 50131 requirements, unit must be 

installed in an approved tamper enclosure.

Do not cut, bend or alter the antennas and ensure that electrical wires do not cross over the antennae as these may affect the signal reception.

EN 50131 Compliancy

In order to meet with EN 50131 compliancy you will require the following:

EN Metal Box (MG5050 EN and SP Series)

Tamper Kit TK278 (MG5050 EN and SP Series)

Tamper Antenna (MG5050 EN only)

Firmware version 4.96 or higher (not applicable for MG5075)

Plastic Box (included with the MG5075)

75W Internal Power Supply (MG5075 only)

Earth Ground

Connect the zone and dialer ground terminals from the control panel to the metallic enclosure (MG5000/MG5050/MG5050EN/SP Series only) and cold water pipe or 
grounding rod as per local electrical codes. 

WARNING: For maximum lightning protection, use separate earth grounds for the zone and dialer grounds as shown in the PCB Layouts for each 
respective panel. For UL installations, the metallic enclosure must be grounded to the cold water pipe.

AC Power

Do not use any switch-controlled outlets to power the transformer in order to avoid accidental user AC shut off. Connect the transformer as shown in Figure 1. Use 
Table 1 for appropriate transformer. For the MG5075, use the supplied internal power supply.

Use only safety approved Transformer with rated output voltage of 16.5Vac and rated power of 40 VA maximum.

Backup Battery

To provide power during a power loss, connect a 12 Vdc 4 Ah rechargeable acid/lead or gel cell backup battery as shown in Figure 1 below. Use a 7 Ah battery to comply 
with UL fire requirements. Connect the backup battery after applying AC power. When installing, verify proper polarity as reversed connections will blow the battery fuse.

Use only safety approved rechargeable battery with rated voltage of 12 Vdc and rated current of 7A maximum.

Battery Test

If the battery is disconnected or if the battery fuse is blown, a No/Low Battery failure will appear in the keypad’s trouble display

 

(See “Trouble Display” on page 63). 

This trouble will also appear if the battery’s capacity is too low or if the voltage drops to 10.5V* or lower while the control panel is running on the backup battery. At 
8.5V** or lower, the panel shuts down and all outputs close.

* For MG5075 low battery trouble will occur if voltage drops to 11.6V or lower.
** For MG5075 panel shutdown will occur at 11.0V.

Figure 1: AC Power and Backup Battery Connections

Transformer:
(use only one of the following)

16 VAC 

20 VA

(not verified by UL)

For UL
16.5 VAC 

40 VA

Panel DC power supply output rated at:

1.1A

1.5A

Maximum allowed current supplied by all Auxiliary 
outputs:

Max: 700 mA

Max: 700 mA
Do not exceed 200 mA for US or Canadian 
installations

Battery Charge Currents

350 mA

350 mA/700 mA (programmable via panel)

UL Warning:

A 12 Vdc / 7 Ah battery is required to comply 
with UL fire requirements.

Caution:

Disconnect battery before replacing the fuse.

WARNING: Improper connection of 
the transformer may result in damage 
to the system.

Rechargeable Battery

UL/ULC - 12 Vdc / 4 Ah or 7Ah

Partial PCB view 

Содержание Magellan MG5050E

Страница 1: ...ation Guide Always Armed Never Disarmed SP5500 SP6000 SP7000 v7 14 SP4000 v5 23 SP65 v5 24 MG5075 v1 01 MG5050 MG5000 v4 90 MG5050E v7 14 32 Zone Wireless Security Systems 4 to 32 Zone Expandable Secu...

Страница 2: ......

Страница 3: ...Transmitter Programming 36 Viewing the Wireless Transmitter Signal Strength 36 Supervision Options 36 RF Jamming Supervision 37 Wireless Serial Number Display 37 Remote Control Programming 37 Wireless...

Страница 4: ...em will prevent personal injury or property damage or in all cases provide adequate warning or protection Your security system should therefore be considered as one of many tools available to reduce r...

Страница 5: ...iew Modules Current Consumption List Module Description Maximum number per system K10V H K32 K32LCD K32LX K35 K636 TM50 TM70 10 and 32 Zone Hardwired LED and LCD Keypad Module Touchscreen 15 total inc...

Страница 6: ...lica Test and Certification Cannot exceed 200 mA for UL installations Cannot exceed 1A for UL installations SP4000 SP5500 SP6000 SP65 SP7000 Power rating 16 5 Vac 50 or 60 Hz minimum 20 VA 40 VA recom...

Страница 7: ...ve panel For UL installations the metallic enclosure must be grounded to the cold water pipe AC Power Do not use any switch controlled outlets to power the transformer in order to avoid accidental use...

Страница 8: ...lash once every second Normal Flashes ON 1 sec and OFF 1 sec Any trouble Always ON Panel is using phone line Fast flash 6 seconds after power up Installer lock enabled RX TX LED Flashes quickly when r...

Страница 9: ...line Fast flash 6 seconds after power up Installer lock enabled RX TX LED Flashes quickly when receiving or transmitting RF signals from wire less devices 5 Antenna 6 Serial Used for connecting the IP...

Страница 10: ...Normal Flashes ON 1 sec and OFF 1 sec Any trouble Always ON Panel is using phone line Fast flash 6 seconds after power up Installer lock enabled AUX LED ON power on Aux OFF No power RF RX RF TX LED FL...

Страница 11: ...h 6 seconds after power up Installer lock enabled 4 Serial Used for connecting the IP Internet Module PCS Data also used for In Field Firmware upgrade through a 307USB Direct Connect Interface 5 Refer...

Страница 12: ...to Panel Reset on page 3 4 Four pin connector can be used for quick installation of a keypad 5 EBUS J3 and Dialer J4 used with VDMP3 Plug In Voice Module for voice reporting PCS Series Communicator M...

Страница 13: ...rging and battery test LED 3 Refer to Panel Reset on page 3 4 Four pin connector can be used for quick installation of a keypad 5 EBUS J3 and Dialer J4 used with VDMP3 Plug In Voice Module for voice r...

Страница 14: ...Reset on page 3 4 Four pin connector can be used for quick installation of a keypad 5 EBUS J3 and Dialer J4 used with VDMP3 Plug In Voice Module for voice reporting PCS Series Communicator Module 6 S...

Страница 15: ...The MG5075 is pre installed in the location shown below If tamper is required remove the MG5075 PCB from the box Install tamper screw and re install the PCB in designated mounting location Please not...

Страница 16: ...16 Magellan Spectra SP Installation Guide SP5500 8x10 SP6000 11x11 SP7000 11x11...

Страница 17: ...nals power bells sirens and other warning devices requiring a steady voltage output during an alarm The bell output supplies 12Vdc upon alarm and can support one 30 watt or two 20 watt sirens The bell...

Страница 18: ...as motion detectors and door contacts are connected to the control panel s zone input terminals Figure 3 demonstrates single zone input terminal connections recognized by the panel Once connected the...

Страница 19: ...re is a software oriented feature that enables two detection devices to be installed per hardwired input terminal Each detection device has its own zone displays its zone status on the keypad and send...

Страница 20: ...section 866 Figure 5 Fire Circuits 4 Wire and 2 Wire Installation For 4 wire installation program the Activation Event so that the smoke detectors can be reset by pressing the CLEAR ENTER keys for thr...

Страница 21: ...tering certain sections eight options will be displayed where each option from 1 to 8 represents a specific feature Press the key corresponding to the desired option This means the option is ON Press...

Страница 22: ...ce Memory Key on the serial connector labeled MEMORY KEY of the Control Panel that you want to copy Make sure the write protect jumper of the Memory Key is on 3 Reapply AC and battery power 4 In Insta...

Страница 23: ...Delete arm Delete whole entry off Toggle numeric alphanumeric keys byp Toggle lower case upper case mem Special characters Label Sections 181 to 212 32 Zone Labels 341 to 356 16 PGM Labels 511 to 542...

Страница 24: ...Press key once Press key twice Press key three times 1 A B G 2 D E Z 3 H Q I 4 K L M 5 N O 6 P R S 7 T U F 8 C Y W Greek Special Characters Catalogue 016 032 048 064 080 096 112 128 144 160 176 192 2...

Страница 25: ...Magellan Spectra SP Installation Guide 25 Russian Special Characters Catalogue Russian Keypad Letter Assignment...

Страница 26: ...34 123456 The Installer Code can be used to program the System Master Code With the System Master Code a user can use any arming method and can program any user access code but not the User Code Optio...

Страница 27: ...the other User Code Options selected Please note that with the Arm Only option the user can cancel a recently armed system by re entering the access code before the end of the exit delay PGM Activatio...

Страница 28: ...validate your path and once for the non path zone If you do not validate the non path zone the system will fall in alarm Entry Exit with a Keypad When entering with a keypad the path zones will fall...

Страница 29: ...g different entry delays is useful when for example one entry point requires a longer delay than the other entry point or in a partitioned system where each partition may require a different entry del...

Страница 30: ...the zone is bypassed by the system See Zone Definition Status on page 32 for any exceptions Follow Full Arm Zones Sections 001 to 032 Zones 1 to 32 First Digits 07 Upon regular arming the zone is Foll...

Страница 31: ...lary Zones Sections 001 to 032 Zones 1 to 32 First Digits 16 when a 24Hr Burglary Zone opens whether the system is armed or disarmed the control panel will immediately generate an alarm This alarm is...

Страница 32: ...anges depending on the arm status and if the Flex Instant delay is enabled See Zone Definition Status on page 32 Zone Partition Assignment Sections 001 to 032 Zones 1 to 32 The control panel provides...

Страница 33: ...larm report code and provides a pulsed output see Figure 9 on page 30 for any bells or sirens connected to the control panel s bell output 4 ON 5 OFF Silent Alarm When the conditions for an alarm are...

Страница 34: ...e on the ZX8 ZX82 ID A Panel 1 a tamper input By default it is a zone Tamper Input on ZX8 ZX82 ID B Panel 9 Section 706 General Zone Options 2 Option 5 OFF Zone B default Option 5 ON Tamper input Enab...

Страница 35: ...ON position for three seconds then turn it to the OFF position Keyswitch Options Each keyswitch zone can be programmed with one or more options Stay Sleep Disarm Option Keyswitch On board hardwire con...

Страница 36: ...be used with any remote controls assigned to the control panel Supervision Bypass Options Section 705 Arming Disarming Options Option 8 ON Generate Supervision Loss if detected on a Bypassed Wireless...

Страница 37: ...0 Press the anti tamper switch of the desired module to be viewed The first digit of the serial number will illuminate on the keypad Press ENTER to see each consecutive digit Press CLEAR to exit Remot...

Страница 38: ...specific keypad For example section 591 is the viewer for keypad 1 and section 598 is the viewer for the keypad 8 Sometimes moving the keypad by a small amount will greatly increase the signal recept...

Страница 39: ...Supervision Enabled default Wireless Keypad Live Display Mode Section 587 Wireless Keypad Options Option 8 OFF Live Display Mode Disabled Option 8 ON Live Display Mode Enabled default Wireless Repeate...

Страница 40: ...t the repeater will retransmit any signals relevant to them Option 1 OFF Repeat Wireless Keypad 1 Signals default Option 1 ON Repeat Wireless Keypad 1 Signals Option 2 OFF Repeat Wireless Keypad 2 Sig...

Страница 41: ...ess Zone 7 Signals Option 8 OFF Repeat Wireless Zone 8 Signals default Option 8 ON Repeat Wireless Zone 8 Signals Section 553 Repeater 1 and Section 563 Repeater 2 Wireless Repeater Options Enable or...

Страница 42: ...ireless Zone 23 Signals Option 8 OFF Repeat Wireless Zone 24 Signals default Option 8 ON Repeat Wireless Zone 24 Signals Section 555 Repeater 1 and Section 565 Repeater 2 Wireless Repeater Options Ena...

Страница 43: ...Signals Option 8 OFF Repeat Wireless 2 Way PGM 8 Signals default Option 8 ON Repeat Wireless 2 Way PGM 8 Signals Section 557 Repeater 1 and Section 567 Repeater 2 Wireless Repeater Options Enable or...

Страница 44: ...ming Disarming Options Option 2 OFF Stay Arming Switches to Stay Force Arming Disabled Option 2 ON Stay Arming Switches to Stay Force Arming Enabled default With this feature enabled the control panel...

Страница 45: ...ction 762 Auto Arm Timer Section 761 Partition 1 762 Partition 2 Select the section corresponding to the desired partition and program the time use the 24 hour clock i e 6 30PM 18 30 that you wish the...

Страница 46: ...siren will squawk once upon arming and twice upon disarming via the keypad Bell Squawk On Arm Disarm with Remote Control Section 704 Arming Disarming Options Option 4 OFF Bell Squawk on Arm Disarm wi...

Страница 47: ...time period to confirm their presence and functionality If a device has not sent a signal within that time period the control panel can generate a trouble an alarm and or transmit a report code to the...

Страница 48: ...ic 3 is Silent default Option 6 ON Panic 3 is Audible Silent alarm The control panel emits a confirmation beep and transmits the appropriate Panic report code if programmed in section 863 The control...

Страница 49: ...ted for the programmed amount of time in the partition Partial Arming A partition was Stay Sleep or Force armed or armed with Bypassed zones Section 861 Quick Arming A partition was armed using a One...

Страница 50: ...elow recommended limits Wireless Zone Low Battery The battery voltage of a wireless transmitter has dropped below recommended limits Wireless Zone Supervision Lost The control panel has lost communica...

Страница 51: ...r any digit from 0 to 9 and any special keys or functions up to a maximum of 32 digits After the maximum dialing attempts See Maximum Dialing Attempts on page 53 to one monitoring station telephone nu...

Страница 52: ...and messages If the reporting codes are set at 0xFF the panel will send the appropriate report code from the Automatic Report Code List in the programming guide Alternatively report codes can be prog...

Страница 53: ...000 to 255 attempts Default 8 attempts The value programmed in section 081 determines how many times the control panel will re dial the same monitoring station telephone number before proceeding to th...

Страница 54: ...station Example The Closing Delinquency Timer for partition 1 in section 719 is programmed for 005 days The control panel verifies when partition 1 was last disarmed at midnight every day If partition...

Страница 55: ...nt zone or silent panic alarm to switch to audible TLM Fail Timer Section 830 016 to 255 x 2 seconds Default 32 seconds If TLM does not detect the existence of a telephone line for the duration of thi...

Страница 56: ...ate deactivate when the programmed PGM Deactivation Event occurs Instead of deactivating the PGM when a specific event occurs the PGM can deactivate after a programmed period elapses See PGM Delay on...

Страница 57: ...of each PGM can be verified in sections 321 to 336 Sometimes moving the PGM or control panel by a small amount will greatly increase the signal reception How Do I Assign PGMs to the Panel 1 Press the...

Страница 58: ...panel is equipped with a partitioning feature which can divide the alarm system into two distinct areas identified as Partition 1 and Partition 2 Partitioning can be used in installations where shared...

Страница 59: ...to using the default Daylight Saving Time DST settings in section 731 you can also set a customized DST Set section 732 for the DST starting period and 733 for the DST ending period Both sections rec...

Страница 60: ...y delay on LCD keypad default When this option is enabled the panel will display entry delays on the K32LCD keypad modules Display Exit Delay on LCD keypad K32LCD Section 701 General System Options Op...

Страница 61: ...e control panel will answer the call This section applies to the Plug in Voice Dialer when using a VDMP3 Panel Identifier Section 910 0000 to FFFF This 4 digit code identifies the control panel to the...

Страница 62: ...90 capacity before attempting to re communicate with the monitoring station When the Event Buffer is full each subsequent new event will erase the oldest event in the buffer Call Back BabyWare Section...

Страница 63: ...ntrol panel 2 AC failure on control panel 3 Auxiliary overload on control panel 4 Wireless keypad AC failure 5 Wireless keypad battery failure 6 Wireless repeater AC failure 7 Wireless repeater batter...

Страница 64: ...Code 50 Bell Squawk On Arm Disarm With Keypad 46 With Remote Control 46 Bypassable Zones 33 C Call Back Feature 62 Cancel Auto Arm Report Code 49 Charge Current 58 Closing Delinquency 54 Cold Start Re...

Страница 65: ...46 No Movement Auto Arming 45 No Movement Report Code 49 Number of Rings 60 Numbers 53 O One Touch Arming 46 Report Code 49 Options Alarm 47 Arming and Disarming 44 Auto Arming 45 User code 26 Zone 3...

Страница 66: ...yD 28 Switch 53 Switch to Stay Arming 44 System 54 Master Code 26 Settings 58 Trouble Report Codes 50 Trouble Restore Codes 49 50 T Tamper Bypass Options 47 Tamper Recognition 47 Telephone Line Connec...

Страница 67: ......

Страница 68: ...n We hope this product performs to your complete satisfaction Should you have any questions or comments please contact us at support paradox com Additional information can be found on our website www...

Отзывы: